  Description

The contact protection pulse relay (switching amplifier, pulse shaper) serves preferably the protection of weak transducer contacts or the amplification of binary transducer signals. At the same time it converts the prepared input signals to output pulses with constant, adjustable lengths (via trimmer at the front). Typical input signals are reed contacts, signal generator according to Namur (DIN EN 60947-5-6), TTL level, voltage signals or resistance changes. Heavy-duty and potential-free contacts are available at the output. The version AD-KI 100 GSO has wear-free transistor outputs, which are also galvanic separated via opto-coupler. Further, the device has an electronic wide-range power pack, which supplies the AD-KI 100 GS(O) energy-efficient from a wide supply voltage range.

  Application

Pulse reception of water meter or flow monitors for metering the through-flow quantity. Amplification and contact protection of weak transducer signals (reed contacts, limit switches, etc.), sound signal transmission in control circuits. Sound amplifier for inductive and capacitive proximity switches according to Namur (DIN 19234).

AD-ki100gs.jpg

  Specific characteristics

  • support for all standard encoder types
  • via front-trimmer adjustable output pulse length
  • LEDs for signal display
  • two independent potential-free relay output (AD-AI 100 GS)
  • two independent semiconductor switches (AD-AI 100 GSO)
  • wide range power supply
  • narrow Design
  •   Business data

    Order number
    AD-KI 100 GS with 2 independent relay outputs
    AD-KI 100 GSO with 2 independent semiconductor outputs

      Download

    PDF

      Technical specifications

    Impulse input
    Min. pulse width 2 ms
    Namur supply voltage ca. 8,2 V DC
    Logic level for Namur signals Low < 1,2 mA ... High > 2,1 mA
    Max. input voltage (active) 30 V DC
    Logic level for active signals Low < 5 V ... High > 20 V
    Type of contact potential-free
    Pulse processing
    Adjustable output pulse length 0,2 ... 10 s (0,5 s factory default)
    Relay outputs
    Maximum switching load AC 250 V, 2 A
    Maximum switching load DC 50 V, 2 A
    Contact construction potential-free changeover
    Switching operations mechanical 10000000
    At 230V/2A AC, cos(phi)=1 600000
    At 230V/2A AC, cos(phi)=0,4 200000
    At 24V/1 A DC 200000
    Semiconductor outputs
    Max switching voltage 30 V DC
    Max. switching current 50 mA DC
    Working voltage at pullup 10 ... 30 V DC
    Internal pullup 5 kOhm
    Supply
    Voltage range AC 50 ... 253 V AC, 50/60 Hz
    Nominal voltage AC 230 V AC
    Voltage range DC 20 ... 253 V DC
    Nominal voltage DC 24 V DC
    Power consumption AC / DC 3 VA / 2W
    Transmission behaviour
    Temperature influence 100 ppm/K
    Response time ~ 5 ms
    Housing
    Dimensions (WxHxD) 23x78x103 mm
    Type of protection IP 20
    Connection method screw clamp
    Terminals, wire cross section 2,5 mm flex wire / 4 mm one wire
    Bolting torque terminals 0,5 Nm
    Weight ~ 115 g
    Manner of fastening 35 mm DIN rail 35mm
    Environmental conditions
    Ambient temperature 0 ... 50 C
    Storage and transport -10 ... 70 C (no thawing)
    EMC
    Product family standard EN 61326 1)
    Emitted interference EN 55011, CISPR11 Cl. B
    Electrical safety requirements
    Product family standard EN 61010-1
    Overvoltage category II
    Pollution degree 2
    Galvanic isolation, test voltages
    Input / output 3,75 kV, 50 Hz (1 min.)
    Signal / supply unit 4 kV, 50 Hz (1 min.)
    Protection circuits
    Input electrical surge protection
    Power supply protection against over voltage, over temperature and reverse polarity
    1) During checking, slight signal deviations are possible.

      Block and wiring diagram

    AD-ki100gs-blockbild_en.svg

      Dimensions

    AD-gs-masszeichnung.svg