Description
The separation amplifier of type family AD-STV 810 serves the galvanic
separation, conversion and amplification of unipolar signal sizes. The very high frequency range allows direct current as well as fast current transfers. Input, output and the supply voltage are galvanically separated from each other. The output signal is independent of the connected load up to a maximum value. The limit frequency of the amplifier can be set at the front as an option.
  Application
Recording, galvanic 3-way separation, conversion and amplification of unipolar measuring sizes (voltage or current).
  Specific characteristics
3dB bandwidth switch (0,1 / 0,5 / 1 / 2 / 20 kHz) are optionally available
  Business data
catalog number |
AD-STV 810 GS |
  Download
|
  Technical specifications
Transmitter supply |
Feeding voltage |
24 ... 20 V (4 ... 20 mA) |
Current limit |
< 30 mA |
Input current |
Measuring range |
0 ... 20 mA 1) |
Input resistance |
25 Ohm |
Input voltage |
Measuring range |
0 ... 10 V 1) |
Input resistance |
100 kOhm (10 kOhm / Volt) |
Output current |
Output range |
-20 ... 20 mA 1) |
Max. burden |
500 Ohm |
Max. residual ripple |
40 ľAss |
Output voltage |
Output range |
-10 ... 10 V 1) |
Min. burden |
1 kOhm |
Max. residual ripple |
20 mVss |
Supply |
Voltage range AC |
50 ... 253 V AC, 50/60 Hz |
Nominal voltage AC |
230 V AC |
Voltage range DC |
20 ... 253 V DC |
Nominal voltage DC |
24 V DC |
Input power AC/DC |
4,4 VA / 2,4 W |
Transmission behaviour |
Basic accuracy |
< 0,2 % |
Temperature influence |
100 ppm/K |
Frequency range |
0...20 kHz (-3dB) |
Housing |
Dimensions (WxHxD) |
23x78x103 mm |
Type of protection |
IP 20 |
Connection method |
screw clamp |
Terminals, wire cross section |
2,5 mm˛ flex wire / 4 mm˛ one wire |
Bolting torque terminals |
0,5 Nm |
Weight |
~ 100 g |
Manner of fastening |
35 mm DIN rail 35mm |
Environmental conditions |
Ambient temperature |
0 ... 50 °C |
Storage and transport |
-10 ... 70 °C (no thawing) |
EMC |
Product family standard |
EN 61326 2) |
Emitted interference |
EN 55011, CISPR11 Cl. B |
Electrical safety requirements |
Product family standard |
EN 61010-1 |
Overvoltage category |
II |
Pollution degree |
2 |
Galvanic isolation, test voltages |
Input / output |
3,75 kV, 50 Hz (1 min.) |
Signal / supply unit |
3,3 kV, 50 Hz (1 min.) |
Protection circuits |
Input |
electrical surge protection |
Output |
electrical surge protection |
Power supply |
Protection against overvoltage reverse polarity |
|
1) Values must be adviced by order. 2) During checking, slight signal deviations are possible. |
|
|