. . HOME GERMAN ENGLISH IMPRINT

Special Functions

Power Supply
AD-SV 1224 GL


back to products

  Description

The power converter AD-SV 1224 GL is for increasing an available low supply voltage to a substantially higher value. An upward regulation switching with a high degree of sufficiency enables the operation of electric measuring converters, which demand a supply voltage of at least 20 V DC. An electric over current protection switches the device securely off during a short circuit at the output. To reset this fuse, a brief voltage separation at the input is necessary.

  Application

A mains supply is not always available at all installation sites. In such cases, one resorts to battery voltages with 12V DC, which are also possibly charged by solar energy. Almost all devices of the AD-device family work from a supply voltage of 20 V DC upwards and therefore can also be operated in remote areas. This also enables operation in vehicles with 12V board voltage.

AD-sv-1224-gl-spannungsversorgung.jpg

  Specific characteristics

  • Increasing a voltage supply to a level required for operating a device.
  • It is not essential that the earth lead for the load is acquired from the AD-SV 1224 GL. The earth connection can also be carried out directly at the feeding voltage source.
  • Electronic overload protection with reverting characteristic and manual hold.
  •   Business data

    catalog number AD-SV 1224 GL

      Download

    PDF

      Technical specifications

    Input
    Input voltage range 11 ... 15 V DC
    Output
    Output voltage range 20 ... 30 V DC
    Max. load 5 W
    Housing
    Dimensions (WxHxD) 18 x 78 x 103 mm
    Type of protection IP 20
    Connection method Schraubklemmen
    Terminals, wire cross section 2,5 mm▓ Litze / 4 mm▓ Draht
    Bolting torque terminals 0,5 Nm
    Weight ~ 100 g
    Manner of fastening 35 mm Normschiene
    Environmental conditions
    Ambient temperature 0 ... 50 ░C
    Storage and transport -10 ... 70 ░C (Betauung vermeiden)
    EMC
    Product family standard EN 61326
    Emitted interference EN 55011, CISPR11 Cl. B
    Electrical safety requirements
    Product family standard EN 61010-1
    Overvoltage category II
    Pollution degree 2
    Galvanic isolation
    Input/output KEINE Trennung! Durchgehende Masseleitung.
    Protection circuits
    Input Schutz gegen ▄berspannung, ▄berstrom
    Output Schutz gegen ▄berspannung, ▄berstrom

      Block and wiring diagram

    AD-sv1224gl_blockbild_de.svg

      Dimensions

    AD-gl-masszeichnung.svg