. . HOME GERMAN ENGLISH IMPRINT

AC Isolation Amplifier
AD-TV 581 GS


back to products

  Description

The alternating current isolation amplifier AD-TV 581 GS detects the true RMS value of an alternating current. The input variable 0-1A AC or 0-5A AC is here freely selectable via terminal. The alternating current is galvanic separated and transformed into an impressed DC standard signal 0/4-20 mA or 0/2-10 VDC. The zero point and the range of the measuring signal can be adjusted with trimmers at the front. The trimmers can be activated via a wire bridge. The start of the output range can be modified via a wire bridge from 0 to 4mA or from 0 to 2V, exceeding the measuring range or falling below the measuring range is indicated with a flashing LED at the front of the device. The device can be configured with a PC software via the interface on the front interface.

  Application

Freely configurable transformation of AC current signals to DC standard signals, with simultaneous galvanic separation.

AD-TV-581-GS-AC-Trennverstaerker.jpg

  Specific characteristics

  • true-rms
  • zero point trimmer and final value trimmer can be switched on
  • programming via optional AD-Studio Configuration software possible
  •   Business data

    catalog number AD-TV 581 GS

      Download

    PDF

      Technical specifications

    Input current
    Measuring range 0 ... 1 A AC / 0 ... 5 A AC 1)
    Input frequency 40 ... 400 Hz
    Overload temporary + 100 % (3 s)
    Overload permanent + 50 %
    Output current
    Max. output range 0 ... 20 mA 1)
    Max. burden 500 Ohm
    Output voltage
    Max. output range 0 .. 10 V 1)
    Min. burden 10 kOhm
    Transmission behaviour
    Trim range +/-20 % 1)
    Linearity error 0,5 % of full scale
    Rise time (90%) 200 ms (min. 50 ms) 1)
    Temperature influence +/- 100 ppm/K
    Supply
    Supply voltage 20 ... 253 V DC / 50 ... 253 V AC
    Max. power consumption 1,2 W / 2,2 VA
    Housing
    Manner of fastening DIN rail 35mm (EN 50022)
    Type of protection IP 20
    Connector cross section max. 2,5 mm
    Bolting torque screw terminals 0,5 Nm
    Weight ca. 110 g
    Environmental conditions
    Ambient temperature 0 ... 50 C
    Storage and transport -10 ... 60 C
    EMC
    Product family standard EN 61326
    Emitted interference EN 55011, CISPR11 Cl. B
    Electrical safety requirements
    Product family standard EN 61010-1
    Overvoltage category II
    Pollution degree 2
    Safety measurement EN 61010-2-030
    Measurement category CAT III
    Galvanic isolation, test voltages
    Input/output 4 kV (1 min)
    Input/power-supply 4 kV (1 min)
    Output/power-supply 3 kV (1 min)
    1) Different values must be advised by order
    2) During electromagnetic disturbance minor changes in output signal are possible.

      Block and wiring diagram

    AD-tv581gs-blockbild.svg

      Dimensions

    AD-gs-masszeichnung.svg