Description
The digital multi-function measuring transformers of series VarioCheck AD-VC 3 are freely programmable digital measuring transducers with two analogue outputs and up to 4 limiting value relays. Extensive standard equipment and additional options solve almost all imaginable tasks of a modern evaluation.
Enter all characteristics directly on the device or use the configuration software „AD-Studio“.
VarioCheck AD-VC 3 fulfils all tasks of a universal and secure measuring value recording through integral function modules
such as limiting value messages, freely adjustable hysteresis, selectable relay functions, time-delayed switching,
automatic or manual simulation modus, free linearizing curves and a wide range of supply voltage.
  Specific characteristics
Bipolar voltage/current inputs
Supply of 2-/3-wire transmitter
Potentiometer input
Current and voltage output, differently scalable and can be utilised simultaneously
Error message with missing or defective sensor at measuring range 4-20 mA
LCD for display of different operating modes, lit in several colours (R/Y/B).
Freely definable scaling of the quantity to be measured through stating range, decimal point position and unit from the list or defined unit.
Zoom function, expanded scale, linearizing, inverse mode
Learning Mode Range
Automatic or manual simulation operation
Monitoring of the measuring signal with up to 4 freely adjustable limiting values
Slave pointer function (saving min. and max. value)
Locking the parameterizing via edit lock
Non-volatile saving of all set parameter
Menu languages switchable to: German, English
Housing GVF, GF and EV
in the housing GVF Pluggable and codable terminal strips
  Business data
Order number |
AD-VC3 GF R0 |
Bauform GF, without relay |
AD-VC3 GF R2 |
Bauform GF, two relays |
AD-VC3 GF R4 |
Bauform GF, four relays |
AD-VC3 GVF R0 |
design GVF, without relay |
AD-VC3 GVF R2 |
design GVF, two relays |
AD-VC3 GVF R4 |
design GVF, four relays |
AD-VC3 EV R2-24V |
Bauform EV, zwei Kontaktausgänge, 24 VDC-Versorgung |
AD-VC3 EV R2-230V |
Bauform EV, zwei Kontaktausgänge, 230 VAC-Versorgung |
  Download
|
  Technical specifications
Input current |
Measuring range |
-20 ... + 20 mA |
Accuracy |
5 µA |
Input resistance |
60 Ohm |
Voltage input 10V |
Measuring range |
-10 ... + 10 V |
Accuracy |
2,5 mV |
Input resistance |
1 MOhm |
Voltage input 1V |
Measuring range |
-1 ... + 1 V |
Accuracy |
250 µV |
Input resistance |
> 1 MOhm |
Potentiometer input |
Connection method |
3-wire system |
Max. Resistance |
100 Ohm ... 100 kOhm |
Transmitter supply |
Off-load voltage |
24,5 V |
Voltage at 20mA |
19,5 V |
Current limit |
~ 25 mA |
Output current |
Max. output range |
0 ... 20,4 mA |
Accuracy |
~ 20 µA |
Max. burden |
500 Ohm |
Residual ripple |
20 µAss |
Output voltage |
Max. output range |
0 ... 10,2 V (EV: 12,5 V) |
Accuracy |
~ 10 mV |
Min. burden |
5 kOhm |
Residual ripple |
10 mVss |
Resolution |
Input |
13 bit |
Output |
10 bit |
Relay outputs A...D |
Contacts R2 / R4 |
2 contacts / 4 contacts |
Max. AC-breaking capacity |
250 V AC, 2 A AC, 50Hz |
Max. DC-breaking capacity |
50 V DC, 2 A DC |
Switching operations |
|
Mechanical |
107 |
AC: 230V / 2A, cos(phi)=1 |
6 * 105 |
AC: 230V / 2A, cos(phi)=0,4 |
2 * 105 |
DC: 24V / 1A |
2 * 105 |
DC: 24V / 1A |
2 * 105 |
Display |
Graphic-LCD |
42x64 Pixel, background RGB lights |
Digital display |
4-digit, can be configured |
Display function |
scaled input signal, input signal, output, limits, scaled dimension as quasi analogue bar, scaling unit |
Transmission behaviour |
Linearity error |
0,2 % of full scale |
Rise time |
100 ms (output auf 90 %) |
Temperature influence |
+/- 100 ppm/K of full scale |
Supply |
Power supply GF/GVF |
20 ... 253 V DC / 50 ... 253 V AC |
Power supply EV |
20..30 VDC or 50...253 VAC |
Max. power consumption GF |
3,0 W / 5,3 VA |
Max. power consumption GVF |
2,6 W / 5 VA |
Max. power consumption EV |
2,6 W / 5 VA |
Housing GF |
Dimensions (WxHxD) |
38,5x78x103 mm |
Type of protection |
IP 20 |
Connection method |
screw clamp |
Terminals, wire cross section |
2,5 mm² flex wire / 4 mm² one wire |
Bolting torque terminals |
0,5 Nm |
Weight |
~ 215 g |
Manner of fastening |
35 mm DIN rail 35mm |
Housing GVF |
Dimensions (WxHxD) |
33x110x134 mm |
Type of protection |
IP 20 |
Connection method |
detachable terminal clamp |
Terminals, wire cross section |
2,5 mm² flex wire / 4 mm² one wire |
Bolting torque terminals |
0,5 Nm |
Weight |
~ 200 g |
Manner of fastening |
35 mm DIN rail 35mm |
Housing EV |
Dimensions (WxHxD) |
30,48x128,4x165 |
Type of protection |
IP00 |
Connection method |
32-pin male connector |
Weight |
~ 300 g |
Manner of fastening |
19"-Eurocard |
Environmental conditions |
Ambient temperature |
-10 ... 60 °C |
Storage and transport |
-10 ... 70 °C (no bedewing) |
EMC |
Product family standard 1) |
EN 61326 |
Emitted interference |
EN 55011, CISPR11 Cl. B |
1)During electromagnetic disturbance minor changes in output signal are possible. |
|
Electrical safety requirements |
Product family standard |
EN 61010-1 |
Overvoltage category |
II |
Pollution degree |
2 |
Galvanic isolation, test voltages |
Input/output |
2,5 kV (1 min) |
Signal/auxiliary voltage |
3 kV (1 min) |
|