AD-LU 410 GT

Description

Especially in power plant operations but also in many other switchgear areas, active power for the optimization and control of processes must be continuously measured. The power converter AD-LU 410 GT is always adapted to the individual case by means of plant-specific adaptations. Due to the fully analog design, fast power measurements are possible, e.g. the detection of short-time load changes. The nominal voltage, the power to be measured and the desired output signal are required by the customer. The exact power values are available as standard signal for further processing.

AD-LU 410 GT

Application

Measurement of the active power in switchgear, power plants, voltage distributions and transformation into an analog standard signal.

Specific characteristics

  • Plug and play installation due to customer-specific production
  • Fast response time due to analog multipliers
  • Measurement of active power in 3- and 4-wire grids
  • Measurement of symmetrical or asymmetrical load
  • Measurement of active power fed back into the grid
  • Analog output also bipolar possible
  • Separate auxiliary voltage with wide range power supply

Business data

Ausführung
1 Phase + N AD-LU 410 GT-1PN
3 Phasen gleich belastet AD-LU 410 GT-3PG
3 Phasen ungleich belastet AD-LU 410 GT-3PU
3 Phasen + N gleich belastet AD-LU 410 GT-3PNG
3 Phasen + N beliebig belastet AD-LU 410 GT-3PNU
Bewertung
Messbereich in kW Bei Bestellung anzugeben
Ausgabebereich in mA/V Bei Bestellung anzugeben
Strom- und Spannungswandler Bei Bestellung anzugeben
Identifiers
EClass 27210124
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf lu410gt.pdf (435 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Voltage inputs
Rated frequency 50/60 Hz
Nominal Voltage Phase/Delta 230/400 V AC
Max. Voltage Phase/Delta 300/520 V AC
Current consumption per phase 0,5 mA AC
Permanent Overload 120% of nominal voltage
Peak load 600 V AC, 1s
Current inputs
Rated current I1, I2, I3 0 ... 1 A AC, 0 ... 5 A AC
Peak load 100 A AC, 1s
Continuous load 6 A AC
Permanent Overload 120% of nominal current
Input resistance per phase ~20 mOhm
Output
Type Current (mA) or voltage (V), to be specified when ordering
Output current
Max. burden 400 Ohm @ 20 mA
Maximum output range -21 ... 21 mA @ 50 Ohm
Output voltage
Min. burden 10 kOhm @ 10 V
Maximum output range -12 ... 12 V (10kOhm)
Accuracy
Accuracy class 0,5% unter Referenzbedingungen
Temperaturdrift cos(phi)=1 ~3 µA/K @ -10...70°C
Frequency influence ~3,5 µA/Hz @ 40 ... 60Hz
Response time 100 ms (10 ... 90)%
Supply
DC 1,6 W @ 20 ... 253 V DC
AC 3,9 VA @ 50 ... 253 V AC
Housing
Type of protection housing IP20
Connection method Screw clamp
Cross section fine wire 2,5 mm2
Cross section one wire 4 mm2
Max. torque of terminals 0,8 Nm
Mounting DIN rail mounting
Weight ~450 g
Environmental conditions
Operating temperature -25 ... 70 °C
Storage, transport -40 ... 70 °C
Electromagnetic compatibility
Product family standard EN 61326-1
Emission EN 55011, CISPR11 Cl. B, Gr. 1
Immission DIN EN 61000-6-5
During an interference effect slight signal deviations are possible.
Electrical safety requirements
Norm DIN EN 61010-1
Overvoltage category III
Measurement category CAT III
Pollution degree 2
Test voltage input/output 5 kV RMS, 1 Min.
Testvoltage output/supply 4 kV RMS, 1 Min.
Product standards
Product family standard EN 60688

Block and wiring diagram

AD-LU 410 GT

Dimensions

AD-LU 410 GT

Circuit examples

AD-LU 410 GT

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com