AD-FM 248 HG

Description

The FM248HG is an analogue transducer for measuring frequency signals and converting them conversion into a linear, analogue current or voltage signal. In order to guarantee stable operation over the long term, all frequency-determining components are permanently are soldered in at the factory and the use of equalisation trimmers is reduced to a minimum. Modifications to the electrical connection signals and frequency must only be carried out by the manufacturer. The device is maintenance-free and contains no mechanical components. A supply voltage of 12 V DC is provided for external additional preamplifiers. A 10-position rotary switch is provided for setting ten different input end frequencies. The setting elements for the final frequency value, full-point controller, zero-point controller and attenuation controller are accessible from the front accessible from the front, allowing flexible use of the device.

AD-FM 248 HG

Application

The main area of application is the speed measurement of machines.

Specific characteristics

  • Factory signal adjustment
  • Adjustment trimmer optional
  • analog signal processing
  • no software

Information

Downloads
Safety instructions pdf ad-safety-instructions.pdf (86 kB)

Technical specifications

Signal input
Input level Min. 0,3 Vss ; max. 100 Vss
DC voltage superposition Max. +/-10V DC
Input impedance > 28 kOhm
Input frequency Min. 0 ... 400 Hz; max. 0 ... 1800 Hz1)
Feeding voltage 12V (+/-10%) ; 25mA
Cable type Shielded and twisted
Output current
Output range 0/4 ... 20 mA1)
Max. burden 750 Ohm
Residual ripple < 50 µAss
Cable type Shielded and twisted
Output voltage
Output range 0/2 ... 10 V1)
Min. burden 1 kOhm
Residual ripple < 20 mVss
Cable type Shielded and twisted
1)Please specify details when ordering. Different input and output values available on request.
Accuracy
Unit < 0,3% of full scale
Temperature influence < 100 ppm / K of full scale
Response time ~ 400 ms
Supply
Voltage range DC 18 ... 30 V DC
Nominal voltage DC 24 V DC
Power consumption DC 1,8 W
Housing
Dimensions (WxHxD) 23 x 109 x 123 mm³
Type of protection IP 20
Connection method Screw clamp
Terminals, wire cross section 0,2...2,5 mm² flex wire / one wire
Bolting torque terminals 0,5...0,6 Nm
Weight ~ 180 g
DIN rail mounting DIN EN 60715
Mounting distance to neighboring devices >= 10 mm
Environmental conditions
Ambient temperature 0 ... 60 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard 2) EN 61326-1
Emitted interference EN 55011 Klasse B
Shielded signal cables must be used for use in industrial environments.
2) During electromagnetic disturbance minor changes in output signal are possible.
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Galvanic isolation, test voltages
Input/output 1 kV RMS (1 min.)
Signal/auxiliary voltage 1 kV RMS (1 min.)
Isolation > 2 MOhm @ 1 kV test voltage for 1 minute (all circuits against each other)

Block and wiring diagram

AD-FM 248 HG

Dimensions

AD-FM 248 HG

Circuit examples

AD-FM 248 HG

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Display and operating elements

Designation Meaning
Damping Sensitivity
Switch positionFrequency range
0300 Hz
1400 Hz
2640 Hz
3720 Hz
4960 Hz
51050 Hz
61280 Hz
71360 Hz
81640 Hz
91720 Hz
Zero Start value (0 %)
Full Maximum value (100 %)
Cookie settings