AD-LU 10 GT

Description

The digital power measuring transducer AD-LU 10 GT measures all quantities of the power-network (current, voltage, energy, harmonics, phase angle, active power, reactive power, apparent power … ) and converts these measuring values onto one freely scalable analogue output (20 mA). In addition, the device also has a transistor output for S0 pulses or for reporting limit values. The unit is therefore optimal suitable for integration in energy management systems. One phase ore balanced 3- or 4-wire systems can be measured. The AD-LU 10 GT is supplied via its measuring voltage L1. The current measuring is carried out via the bar-type transformer mounted on the front. For measuring of high voltages or high currents, external transformers can be connected in series at any time. The AD-LU 10 GT can be read out and parameterised via the integral interface with the aid of the available AD-Studio. An LED at the front signals the operating condition. The compact type of construction and the high performance ability with simultaneous low energy consumption allows usage in almost any application.

AD-LU 10 GT

Application

Typical usage in industrial plant, machines or energy management systems for balancing and determination of energy distribution.
Attention: This is a Class A product according to EN 55011. Additional EMC actions may be necessary when used in small businesses or in residential areas.

Specific characteristics

  • compact design
  • current measurement via clamp on current transfomrers
  • supplied via its measuring voltage L1
  • current output (mA)
  • S0- or Limit-Output
  • monitoring all variables of the three-phase network
  • parameterization via AD-Studio

Business data

Order number
Power measurement transducer AD-LU 10 GT
AD-LU 10 GT
Accessory (optional)
VarioPass3 USB-inetrface adapter
AD-Studio Configuration software
Identifiers
EClass 27210124
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-lu10gt.pdf (226 kB)
Tender text zip lu10gt.zip (19 kB)
STEP file step gt2a.step (3 MB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Input current
Measuring ranges 0 ... 1 A AC; 0 ... 5 A AC;
0 ... 20 A AC
Max. conductor diameter 4,8 mm
Max. measurable harmonic 40
Input voltage
Measuring range 80 ... 253 V AC
Input resistance > 900 kOhm
Output current
Output range 0/4 ... 20 mA
Max. load 400 Ohm
Resolution 11 Bit
Residual ripple 25 µAss
Transistor output
Max. switching load 30 V DC, 20 mA
Pulse length min ... max 50 ms ... 10000 ms
Supply
Voltage range AC 80 ... 253 V AC, 50/60 Hz (see voltage-inputs)
Nominal voltage AC 230 V AC
Power consumption Max. 4 VA
Transfer behavior - in reference to the current value
Basic accuracy < 0,5 % (class 0.5)
Temperature influence 80 ppm/K
Response time < 0,5 s
Housing
Dimensions (WxHxD) 35,5x90x70 mm
Type of protection IP 20
Connection method Screw clamp
Terminals, wire cross section 2,5 mm² flex wire / 4 mm² one wire
Bolting torque terminals 0,6 Nm
Skinning length 6 mm
Weight ~ 150 g
Manner of fastening 35 mm DIN rail 35mm
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1 1)
Emitted interference EN 55011, CISPR11 Cl. A, Gr. 1
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Safety measurement EN 61010-2-030
Measurement category CAT II
Galvanic isolation, test voltages
Grid side to analoge output 4 kV, 50 Hz (1 min.)
Power Supply to Transistor Output 4 kV, 50 Hz (1 min.)
Protection circuits
Input Electrical surge protection
Power supply Protection against over-temperature, over-voltage and over-current
Analogue output Electrical surge protection
1) During checking, slight signal deviations are possible.

Block and wiring diagram

AD-LU 10 GT

Dimensions

AD-LU 10 GT