AD-STV 24 GVB

Description

The supply isolation amplifier AD-STV 24 GVB serves the galvanic isolation and amplification of current signals in the range 0/4...20 mA. The transmitter is supplied by an isolated and limited supply voltage. Input, output and power supply are galvanically isolated. An integral, electronic power pack is designed with a voltage range of 11 to 30 VDC, also for 12V battery voltage. In combination with the small shape, high packing densities can be achieved.

AD-STV 24 GVB

Application

Supply of 2-wire transmitters like pressure or temperature transmitters and galvanic signal isolation.

Specific characteristics

  • 3-way isolation of input, output and supply
  • Current transfer ratio 1:1, input = output
  • Integrated current-limited power supply
  • Suitable for battery voltage of 12VDC

Business data

Order number
AD-STV 24 GVB
Identifiers
EClass 27210120
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Technical specifications

Input current
Measuring range 0 ... 20 mA; 4 ... 20 mA
Input resistance 50 Ohm
Transmitter supply
Open-circuit voltage < 23 V
At 20 mA > 17 V
Current limit < 30 mA
Output current
Output range 0 ... 20 mA; 4 ... 20 mA
Max. burden < 300 Ohm
Transmission behaviour
Basic accuracy < 0,2 %
Linearity error < 0,2 %
Temperature influence < +/-100 ppm/K
Response time < 1 ms
Supply
Voltage range 11 ... 30 V DC
Power consumption 1,4 W
Housing
Dimensions (WxHxD) 13x110x134 mm
Type of protection IP 20
Connection method Detachable terminal clamp (2,5 mm² flex wire / 4 mm² one wire)
Bolting torque terminals 0,5 Nm
Manner of fastening DIN rail 35mm (EN 50022)
Weight Ca. 100 g
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
During electromagnetic disturbance minor changes in output signal are possible.
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Galvanic isolation, test voltages
Input/output 3,75 kV, 1 min
Signal/auxiliary voltage 3 kV, 1 min

Block and wiring diagram

AD-STV 24 GVB

Dimensions

AD-STV 24 GVB