AD-SWG 211 GS

Description

With the setpoint encoder AD-SWG 211 GS setpoints in the form of analog signals can be set by adjustable Coding switch. The range is 0 ... 99 % of the final value and is set on the front in steps of 1%. The output is galvanically isolated from the supply voltage and up to the maximum resistance independent of the connected load. It can be selected between current or voltage output. Due to the highly efficient integrated wide range power supply high output loads are achieved with low power consumption.

AD-SWG 211 GS

Application

For presetting analog set values in measurement and control systems, for simulating analog measurement signals, etc.

Specific characteristics

  • frontal coding switch for setpoint
  • Current or voltage output
  • Wide range power supply

Business data

Order number
ADSWG211GS23 Setpoint range 0 ... 20 mA
ADSWG211GS43 Setpoint range 4 ... 20 mA
ADSWG211GS13 Setpoint range 0 ... 10 V
AD-SWG 211 GS
Identifiers
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-swg211.pdf (167 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Coding switch
Setting range 0 ... 99 % (1%- steps)
Output current
Output range 0 ... 20 mA, 4 ... 20 mA1)
Max. burden 500 Ohm
Residual ripple 20 µAss
Output voltage
Output range 0 ... 10 V, 2 ... 10 V 1)
Min. burden 500 Ohm
Residual ripple 50 mVss
Supply
Voltage range AC 50 ... 253 V AC, 50/60 Hz
Nominal voltage AC 230 V AC
Voltage range DC 20 ... 253 V DC
Nominal voltage DC 24 V DC
Power consumption AC / DC 2 VA / 1 W
Transmission behaviour
Accuracy < 0,2 %
Temperature influence 50 ppm/K
Response time ~ 200 ms
Housing
Dimensions (WxHxD) 23x78x103 mm
Type of protection IP 20
Connection method Screw clamp
Terminals, wire cross section 2,5 mm² flex wire / 4 mm² one wire
Bolting torque terminals 0,5 Nm
Weight ~ 100 g
Manner of fastening 35 mm DIN rail 35mm
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1 2)
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Galvanic isolation, test voltages
Signal / supply unit 4 kV (1 min.)
Protection circuits
Input Electrical surge protection
Output Electrical surge protection
Power supply Electrical surge and reverse current protection
1) Specify signal range in plain text when ordering.
2) During electromagnetic disturbance minor changes in output signal are possible.

Block and wiring diagram

AD-SWG 211 GS

Dimensions

AD-SWG 211 GS

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Cookie settings