AD-SWK 6 WG

Description

With the current converter AD-SWK 6 WG up to three independent alternating current magnitudes can be converted to three alternating voltages of 0-10 V. The frequency-response curve at the output is equivalent to input. There are 3 switchable input ranges available. Inputs, outputs and supply voltage are galvanically separated from each other. The outputs refer to a common mass. An integral electronic wide range power pack with high efficiency prevents strong increase in heat.

AD-SWK 6 WG

Application

For conversion of up to three alternating currents to three alternating voltages

Business data

Order number
AD-SWK 6 WG
Identifiers
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-swk6.pdf (199 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Input
Measuring range 0 ...1,5 / 2 / 3 A AC amplitude - switchable
Max. measurable harmonic 80 (4 kHz)
Ct size (inside diameter) <8 mm
Permanent overload 120 % of the rated value
Temporary overload (1s) Rated value x 20
Output
Output range 0 ... 10 V AC amplitude (7,07 V ACeff)
Min. burden 10 kOhm
Accuracy
Unit <0,5 %
Temperature influence <100 ppm / K
Phase backfill Input/Output Output 3,6° lagging
Supply
Supply voltage AC 50 ... 253 V AC
Nominal voltage AC 230 V AC
Supply voltage DC 20 ... 253 V DC
Nominal voltage DC 24 V DC
Power consumption AC / DC 1,8 VA / 0,8 W
Housing
Connection method input Split core current transformer
Connection method Spring force terminal
Manner of fastening 35 mm DIN rail 35mm
Dimensions (WxHxD) 138x80x64(88)mm
Weight 280 g
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
During checking, slight signal deviations are possible
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Safety measurement EN 61010-2-030
Measurement category CAT III
Galvanic isolation, test voltages
Input/output 2,2 kV AC + Test voltage of the cable of minimum 1000 V
Signal/auxiliary voltage 3 kV RMS
Working voltage 300 V AC/DC
Protective systems
Input/output Over voltage and over current
Power supply Over voltage, over current and over temperature

Block and wiring diagram

AD-SWK 6 WG

Dimensions

AD-SWK 6 WG

We only use technically necessary cookies to improve the user-friendliness of our site.
Cookies for analysis and marketing purposes are not used!
You can find further information in our privacy policy.
made with ♡ by andres.media