AD-TV 22 GVB

Description

The separation amplifier AD-TV 22 GVB serves the galvanic separation and amplification of DC-current signals (0/4-20 mA). The output signal follows linear the input dimension and is independent of the connected burden up to a limiting value. Input, output and supply voltage are galvanically separate from each other with high insulation. An integral electronic power pack with a high degree of effectiveness prevents strong heating and allows high output loads. A high packing density is achieved in combination with a narrow type of construction.

AD-TV 22 GVB

Application

Burden amplification and galvanic decoupling of active DC-current signals in a cost-effective build-up.

Specific characteristics

  • Supply buffer amplifier for 3-way separation of 0/4-20 mA signals (output follows input 1:1)
  • 13 mm narrow housing

Business data

Order number
AD-TV 22 GVB
Identifiers
EClass 27210120
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Technical specifications

Input current
Measuring range 0 ... 20 mA; 4 ... 20 mA
Input resistance 50 Ohm
Output current
Output range 0 ... 20 mA; 4 ... 20 mA
1:1 to the input signal
Max. burden 400 Ohm
Residual ripple <25 µAss
Transmission behaviour
Basic accuracy < 0,2 %
Temperature influence < 100 ppm/K
Supply
Supply voltage 20 ... 253 V DC / 50 ... 253 V AC
Nominal voltage 24 V DC / 230 V AC
Power consumption 0,9 W / 2 VA
Housing
Dimensions (WxHxD) 13x110x134 mm
Type of protection IP 20
Connection method Detachable terminal clamp (2,5 mm² flex wire / 4 mm² one wire)
Bolting torque terminals 0,5 Nm
Manner of fastening DIN rail 35mm (EN 50022)
Weight Ca. 100 g
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1 1)
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
1)During electromagnetic disturbance minor changes in output signal are possible.
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Galvanic isolation, test voltages
Input/output 3,75 kV RMS (1 min.)
Signal/auxiliary voltage 3 kV RMS (1 min.)
Protective systems
Input/output Electrical surge protection
Power supply Electrical surge and reverse current protection

Block and wiring diagram

AD-TV 22 GVB

Dimensions

AD-TV 22 GVB

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Cookie settings
made with ♡ by andres.media