AD-TV 2 GX

Description

The isolation amplifier AD-TV 2 GX, with a construction width of only 6.2 mm, serves the galvanic separation of DC current signals. The output signal follows linear the input variable and is, up to a limiting value, independent of the connected burden (0/4-20 mA, 1:1 input/output). Due to the narrow design, a high packing density is achieved. In combination with a DIN rail connector, the wiring is considerably reduced.

AD-TV 2 GX

Application

Burden amplification and galvanic disconnection of impressed DC current signals.

Specific characteristics

  • narrow 6.2mm construction
  • Supply via DIN rail connector

Business data

Order number
AD-TV 2 GX
Accessory
DIN-rail connector AD-GX Connector
Identifiers
EClass 27210120
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-tv2gx.pdf (189 kB)
Tender text zip tv2gx.zip (577 Bytes)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Input current
Measuring range 0 ... 20 mA
Input resistance 50 Ohm
Output current
Output range 0 ... 20 mA
Max. burden 400 Ohm
Residual ripple < 0,1 %
Open-circuit voltage < 13V
Transmission behaviour
Response time < 50 ms (10-90 %)
Linearity error < 0,1 %
Temperature influence < 70 ppm/K
Supply
Voltage range 18 ... 30 V DC
Nominal voltage 24 V DC
Power consumption < 850 mW
Housing
Dimensions (WxHxD) 6,2 x 92 x 101 mm³
Manner of fastening DIN rail 35mm EN 50022
Type of protection IP 20
Connection method Screw clamp (2,5 mm² flex wire / 4 mm² one wire)
Bolting torque terminals 0,5 Nm
Weight ~ 70 g
Environmental conditions
Ambient temperature -10 ... +50 °C
Storage and transport -10 ... +70 °C (no condensation)
EMC
Product family standard EN 61326-1
During electromagnetic disturbance minor changes in output signal are possible.
Emitted interference EN 55011, CISPR11 Cl. A, Gr. 1
Warning:
This device is not intended to be used in residential areas and can not ensure adequate protection of radio reception in such environments.
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Galvanic isolation, test voltages
Input/output 1,5 kV, 1 min
Signal/auxiliary voltage 1,5 kV, 1 min

Block and wiring diagram

AD-TV 2 GX

Dimensions

AD-TV 2 GX

CAD / CAE Daten

Under "Generate CAD", select the desired CAD model for this product.
For this purpose, registration with our CAD database "PARTcommunity" is required.
The complete CAD product overview can be found at: adamczewski.partcommunity.com

AD-TV 2 GX

Display and operating elements

Designation LED Meaning
On green Power supply
Cookie settings
made with ♡ by andres.media