AD-TV 350 GVF

Description

The bipolar high-current isolation amplifier AD-TV 350 GVF is used for the galvanic isolation, transformation and amplification of bipolar current or voltage signals. The device allows the transmission of direct as well as alternating current signals up to a high frequency range. The high-current output can supply currents up to 200 mA. Thanks to the integrated 3-way isolation, the input, output and supply voltage are high electrically isolated from each other. The efficient wide-range power supply of the AD-TV 350 GVF allows operation in a wide supply voltage range.

AD-TV 350 GVF

Application

Detection, transformation and amplification of fast changing bipolar signals (current or voltage). Directly controlling e.g. Control valves through the high current output.

Specific characteristics

  • bipolar input
  • bipolar high current output
  • wide-range power supply

Business data

Order number
AD-TV 350 GVF Please specify input and output data. Example. E: +/- 20 mA; A: +/- 200 mA
AD-TV 350 GVF
Identifiers
EClass 27210120
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-tv350gvf.pdf (184 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Input current
Measuring range +/- 20 mA
Input resistance Ca. 25 Ohm
Input voltage
Measuring range +/- 10 V
Input resistance Ca. 100 kOhm
Output current
Output range +/- 200 mA
Max. burden 40 Ohm @ 200 mA
Residual ripple 300 µAss @ 200 mA
Output voltage
Output range +/- 10 V
Min. burden 100 Ohm @ 10 V
Residual ripple 40 mVss @ 10 V
Supply
Voltage range AC 50 ... 253 V AC, 50/60 Hz
Nominal voltage AC 230 V AC
Voltage range DC 20 ... 253 V DC
Nominal voltage DC 24 V DC
Power consumption AC / DC 5 VA / 3 W
Transmission behaviour
Basic accuracy < 0,2 %
Temperature influence 70 ppm/K
Cut-off frequency Ca. 1,5 kHz (-3 dB)
Phase shift I/O Ca. 7,5 °
Power-on drift Ca. 0,1 %
Housing
Dimensions (WxHxD) 33x110x134 mm
Type of protection IP 20
Connection method Detachable terminal clamp
Terminals, wire cross section 2,5 mm² flex wire / 4 mm² one wire
Bolting torque terminals 0,5 Nm
Weight ~ 200 g
Manner of fastening 35 mm DIN rail 35mm
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1 1)
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Galvanic isolation, test voltages
Signal / supply unit 3 kV, 50 Hz (1 min.)
Input / output 2,5 kV, 50 Hz (1 min.)
Protection circuits
Input Electrical surge protection
Output Electrical surge protection
Power supply Electrical surge and reverse current protection
1) During checking, slight signal deviations are possible.

Block and wiring diagram

AD-TV 350 GVF

Dimensions

AD-TV 350 GVF

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Cookie settings
made with ♡ by andres.media