AD-TV 380 GA

Description

The isolating amplifier of the type family AD-TV 380 serves the galvanic isolation, conversion and amplification of analog signal magnitudes. By using the front mounted zero and gain trimmers, the output signal can be adjusted.The output is designed for currents up to 200 mA. Input, output and supply voltage are galvanically isolated from each other. The output signal is independent of the connected load up to a maximum value.

AD-TV 380 GA

Application

For registration, galvanic 3-way separation, conversion and amplification of bi-polar measuring magnitudes (voltage or current)

Specific characteristics

  • zero and gain trimmers
  • high-efficiency power supply unit with a range of 20 ... 30 V DC
  • bipolar input
  • high current Output

Business data

Order number
AD-TV 380 GA

Information

Downloads
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Input current
Measuring range +/- 0/4 ... 20 mA
Input resistance 50 Ohm
Input voltage
Measuring range +/- 0/2 ... 10 V
Input resistance 100 kOhm
Output current
Output range Max. 0 ... 200 mA
Max. burden 40 Ohm at 200 mA
Residual ripple 20 µAss
Supply
Voltage range DC 20 ... 30 V DC
Nominal voltage DC 24 V DC
Power consumption DC 6 W
Transmission behaviour
Basic accuracy < 0,2 %
Temperature influence < 100 ppm/K
Response time ~ 1 ms (smaller on request)
Housing
Dimensions (WxHxD) 100x119x73 mm
Type of protection IP 20
Connection method Screw clamp
Terminals, wire cross section 2,5 mm² flex wire / 4 mm² one wire
Bolting torque terminals 0,5 Nm
Weight ~ 300 g
Manner of fastening 35 mm DIN rail 35mm
Environmental conditions
Ambient temperature 0 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326 1)
Emitted interference EN 55011, CISPR11 Cl. B
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Galvanic isolation, test voltages
Input / output 3,75 kV, 50 Hz (1 min.)
Signal / supply unit 2 kV, 50 Hz (1 min.)
Protection circuits
Input Electrical surge protection
Output Electrical surge protection
Power supply Protection against overvoltage, overcurrent and reverse polarity
1) During checking, slight signal deviations are possible.

Block and wiring diagram

AD-TV 380 GA

Dimensions

AD-TV 380 GA

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com