AD-TV 511 GS, AD-TV 551 GS

Description

The isolation amplifiers of type AD-TV 511 GS and AD-TV 551 GS serve as registry of sine wave alternating currents of sizes 0-1A AC and 0-5A AC. The alternating current is galvanically separated and converted to an impressed OC-standard signal. The alternating currents are supplied to the unit via high current connectors, external shunts are therefore obsolete. The output signals are amplified and are independent of the connected load up to a maximum value. The signals can be adapted to the application via a frontal trimmer.

AD-TV 511 GS, AD-TV 551 GS

Application

Adaptation of current transformer signals to DC standard signals by simultaneous galvanic isolation and amplification.

Business data

Order number
AD-TV 511 GS Eingang 0 ... 1 A AC
AD-TV 551 GS Eingang 0 ... 5 A AC

Information

Downloads
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Input
Measuring range 0 ... 1 A AC / 0 ... 5 A AC 1)
Input frequency 40 ... 400 Hz
Overload temporary + 100 % (3 s)
Overload permanent + 50 %
Output
Max. output range 0/4 ... 20 mA 1)
Max. burden 500 Ohm
Max. output range 0 .. 10 V 1)
Min. burden 1 kOhm
Transmission behaviour
Linearity error 0,5 % of full scale
Rise time (90%) 700 ms
Temperature influence +/- 100 ppm/K
Supply
Supply voltage 20 ... 253 V DC / 50 ... 253 V AC
Max. power consumption 1,7 W / 3,5 VA
Housing
Manner of fastening DIN rail 35mm (EN 50022)
Type of protection IP 20
Connector cross section Max. 2,5 mm²
Bolting torque screw terminals 0,5 Nm
Weight Ca. 110 g
Environmental conditions
Ambient temperature 0 ... 50 °C
Storage and transport -10 ... 60 °C
EMC
Product family standard EN 61326
Emitted interference EN 55011, CISPR11 Cl. B
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Safety measurement EN 61010-2-030
Measurement category CAT III
Galvanic isolation, test voltages
Input/output 4 kV (1 min)
Input/power-supply 4 kV (1 min)
Output/power-supply 3 kV (1 min)
1)Values must be advised by order
2) During electromagnetic disturbance minor changes in output signal are possible.

Block and wiring diagram

AD-TV 511 GS, AD-TV 551 GS

Dimensions

AD-TV 511 GS, AD-TV 551 GS

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Cookie settings