AD-TV 581 GS

Description

The alternating current isolation amplifier AD-TV 581 GS detects the true RMS value of an alternating current. The input variable 0-1A AC or 0-5A AC is here freely selectable via terminal. The alternating current is galvanic separated and transformed into an impressed DC standard signal 0/4-20 mA or 0/2-10 VDC. The zero point and the range of the measuring signal can be adjusted with trimmers at the front. The trimmers can be activated via a wire bridge. The start of the output range can be modified via a wire bridge from 0 to 4mA or from 0 to 2V, exceeding the measuring range or falling below the measuring range is indicated with a flashing LED at the front of the device. The device can be configured with a PC software via the interface on the front interface.

AD-TV 581 GS

Application

Freely configurable transformation of AC current signals to DC standard signals, with simultaneous galvanic separation.

Specific characteristics

  • true-rms
  • zero point trimmer and final value trimmer can be switched on
  • programming via optional AD-Studio Configuration software possible

Business data

Order number
AD-TV 581 GS
Identifiers
EClass 27210123
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Technical specifications

Input current
Measuring range 0 ... 1 A AC / 0 ... 5 A AC 1)
Input frequency 40 ... 400 Hz
Overload temporary + 100 % (3 s)
Overload permanent + 50 %
Output current
Max. output range 0 ... 20 mA 1)
Max. burden 500 Ohm
Output voltage
Max. output range 0 .. 10 V 1)
Min. burden 10 kOhm
Transmission behaviour
Trim range +/-20 % 1)
Linearity error 0,5 % of full scale
Measuring time 20 ms (1 Period)
Rise time (90%) 200 ms (min. 60 ms) 3)
Response time 220 ms (min. 80 ms) 3)
Temperature influence +/- 100 ppm/K
Supply
Supply voltage 20 ... 253 V DC / 50 ... 253 V AC
Max. power consumption 1,2 W / 2,2 VA
Housing
Manner of fastening DIN rail 35mm (EN 50022)
Type of protection IP 20
Connector cross section Max. 2,5 mm²
Bolting torque screw terminals 0,5 Nm
Weight Ca. 110 g
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 60 °C
EMC
Product family standard EN 61326-1
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Safety measurement EN 61010-2-030
Measurement category CAT III
Galvanic isolation, test voltages
Input/output 4 kV (1 min)
Input/power-supply 4 kV (1 min)
Output/power-supply 3 kV (1 min)
1) Different values must be advised by order
2) During electromagnetic disturbance minor changes in output signal are possible.
3) Filter 5 (Filter 0).

Block and wiring diagram

AD-TV 581 GS

Dimensions

AD-TV 581 GS

CAD / CAE Daten

Under "Generate CAD", select the desired CAD model for this product.
For this purpose, registration with our CAD database "PARTcommunity" is required.
The complete CAD product overview can be found at: adamczewski.partcommunity.com

AD-TV 581 GS