AD-TWT 24 GM

Description

The isolation transmitter AD-TWT 24 GM in 2-wire-transmitter technique impress into a supply voltage a standard measurement signal of 4-20 mA. The output signal follows linear the input signal up to a maximum value. The connection of an additional auxiliary voltage is not necessary. It obtains its auxiliary energy from the transmitter supply.

AD-TWT 24 GM

Application

Economical galvanical isolation of a active analog signal in a impressed passive 4-20mA signal ( 2-wire-transmitter technique).

Specific characteristics

  • 2-wire-transmitter technique, low amount of cabling
  • output signal of 4-20 mA independent from supply voltage
  • compact design (DIN rail)

Business data

Order number
AD-TWT 24 GM
Identifiers
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-twt24gm.pdf (67 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Input current
Measuring range 4 ... 20 mA
Required input voltage 2,7 V (4 V no load)
Transmitter output
Output range 4 ... 20 mA
Feeding voltage 8 - 30 V DC
Residual ripple Max. 0,5 % of full scale
Transmission behaviour
Basic accuracy < 0,2 %
Temperature influence 150 ppm/K
Response time ~ 700 ms
Housing
Dimensions (WxHxD) 13x78x103 mm
Type of protection IP 20
Connection method Screw clamp
Terminals, wire cross section 2,5 m² flex wire / 4 mm² one wire
Bolting torque terminals 0,5 Nm
Weight ~ 100 g
Manner of fastening 35 mm DIN rail 35mm
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1 1)
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Maximum permanent working voltage across the galvanic isolation 45 V DC
Galvanic isolation, test voltages
Input / output 510 V, 50 Hz (1 min.)
Protection circuits
Input Electrical surge and reverse current protection
Output Electrical surge protection
1) During checking, slight signal deviations are possible.

Block and wiring diagram

AD-TWT 24 GM

Dimensions

AD-TWT 24 GM

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Cookie settings
made with ♡ by andres.media