AD-ER 01 GS

Description

The electrodes are supplied with alternating voltage. If a conduction liquid i.e. water, bridges the mass and the max-electrode, the output relay responds, the transmitter power monitor lights up. Furthermore an internal, commutator ensures that the min-electrode becomes effective. The relay de-energize, if the mass and the min-electrode are not conductive connected. The sensitivity can be adjusted to the given circumstances via an integral trimmer.

AD-ER 01 GS

Application

Monitoring and regulating levels of conductive liquids, especially water.

Specific characteristics

  • 3 input electrodes
  • AC current measurement
  • universal wide range power supply

Business data

Order number
AD-ER 01 GS
Identifiers
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-er01gs.pdf (266 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Electrodes
Voltage < 10 V~
Current < 1 mA
Frequency ~ 45 Hz
Sensitivity 0 ... 60 kOhm
Response time ~ 10 ms
Relay output
Maximum switching load AC 250 V, 2 A
Maximum switching load DC 50 V, 2 A
Contact construction Potential-free changeover
Switching operations mechanical 10000000
At 230V/2A AC, cos(phi)=1 600000
At 230V/2A AC, cos(phi)=0,4 200000
At 24V/1 A DC 200000
Supply
Voltage range AC 50 ... 253 V AC, 50/60 Hz
Nominal voltage AC 230 V AC
Power consumption AC 3 VA
Voltage range DC 20 ... 253 V DC
Nominal voltage DC 24 V DC
Power consumption DC 1,4 W
Housing
Dimensions (WxHxD) 23x78x103 mm³
Type of protection IP 20
Connection method Screw clamp
Terminals, wire cross section 2,5 mm² flex wire / 4 mm² one wire
Bolting torque terminals 0,5 Nm
Weight ~ 100 g
Manner of fastening 35 mm DIN rail 35mm
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1 1)
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Galvanic isolation, test voltages
Input / output 3 kV, 50 Hz (1 min.)
Signal / supply unit 3 kV, 50 Hz (1 min.)
Protection circuits
Input Electrical surge protection
Output Electrical surge protection
Power supply Protection against overvoltage
reverse polarity
1)During electromagnetic disturbance minor changes in output signal are possible.

Block and wiring diagram

AD-ER 01 GS

Dimensions

AD-ER 01 GS

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Display and operating elements

Front Meaning
On LED green, Power supply
response Sensitivity: 0 ... 60 kOhm
Output LED red, Output state
Cookie settings
made with ♡ by andres.media