AD-FM 210 GS

Description

The frequency converter AD-FM 210 GS is adapted ex works for user-side sensors and delivered exactly calibrated for the application. He can supply an initiator or a contact. Default switching thresholds are set for active signals. The required data must be given when ordering the device. The input pulse train is converted into a proportional impressed analog signal. The output signal is independent of the connected load up to a maximum value.

AD-FM 210 GS

Application

The main area of application is flow measurement in water meters, other applications are energy consumption measurements, wind and speed measurements, etc. All common encoder types can be used: initiator according to NAMUR (DIN-EN 60947-5-6), 3-wire optical encoder, reed contacts, transistor outputs and other initiators .

Specific characteristics

  • Wide range power supply
  • Factory signal adjustment
  • Adjustment trimmer optional
  • analog signal processing
  • no software
  • Status LEDs

Business data

Order number
AD-FM 210 GS
Order details:
Signaling device Type & Connection technology
Frequency Range
Analog output signal MA / V
Output signal Range
Response time Seconds
Identifiers
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-fm210gs.pdf (166 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Digital input
Input NAMUR (EN 60947-5-6), reed contact, open-collector, 3-lead opto-transmitteror 24V active1)
Input frequency Min. 0 ... 500 Hz; max. 0 ... 20 kHz1)
Frequency generator supply Active: 8V / 8mA1)
Output current
Output range 0 ... 20 mA1)
Max. burden 500 Ohm
Residual ripple < 50 µAss
Output voltage
Output range 0 ... 10 V1)
Min. burden 500 Ohm
Residual ripple < 20 µVss
1)Specify in plain text when ordering.
Accuracy
Unit < 0,3%
Temperature influence < 100 ppm / K
Response time ~ 200 ms
Supply
Voltage range AC 50 ... 253 V AC, 50/60 Hz
Nominal voltage AC 230 V AC
Voltage range DC 20 ... 253 V DC
Nominal voltage DC 24 V DC
Power consumption AC / DC 2,5 VA / 1,2 W
Housing
Dimensions (WxHxD) 23 x 78 x 103 mm³
Type of protection IP 20
Connection method Screw clamp
Terminals, wire cross section 2,5 mm² flex wire / 4 mm² one wire
Bolting torque terminals 0,5 Nm
Weight ~ 200 g
Manner of fastening 35 mm DIN rail 35mm
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard 2) EN 61326-1
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
In a critical EMC environment, shielded encoder cables are recommended.
2) During electromagnetic disturbance minor changes in output signal are possible.
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Galvanic isolation, test voltages
Input/output 2 kV RMS (1 min.)
Signal/auxiliary voltage 3 kV RMS (1 min.)

Block and wiring diagram

AD-FM 210 GS

Dimensions

AD-FM 210 GS

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Display and operating elements

Designation Meaning
Power LED green, Power supply
Input LED red, Input signal
Zero Trimmer 0 %-Value
Span Trimmer 100 %-Value
Cookie settings