AD-IU 214 GVC

Description

The pulse divider AD-IU 214 GVC detects pulses arriving the input and gives out divided or multiplied pulses via its relay or transistor outputs. The input can be assessed freely. For evaluation of the input only whole number factors or divisors are possible. Mechanical contacts, NAMUR transmitter, active signals and semi-conductor switches can be connected and evaluated. The device can be parameterized by the customer via the optional PC configuration software AD-Studio, however, it can also be delivered preset. The inputs and outputs as well as the power pack are galvanic separated with high insulation. The transfer function of the device is: O = (I*(F1/D1)) O = output, I = input, F = factor, D = divisor

AD-IU 214 GVC

Application

Dividing of any quantity signals, such as through-flows or energy. Application example of energy balance: Input: 1000 Imp/kWh Output: 10 Imp/kWh

Specific characteristics

  • freely assessable impulse input
  • relay output or transistor output
  • integral wide-range power pack
  • compatible with many types of transmitters
  • max. input frequency 1 kHz
  • only 18 mm construction width
  • screw terminals can be pulled off
  • can be parameterized via PC (AD-Studio)

Business data

Order number
AD-IU 214 GVC Relay output
AD-IU 214 GVCO Transistor output
Identifiers
Customs tariff number / country of origin 8538 90 91 / Deutschland

Information

Downloads
Data sheet pdf en-iu214gvc.pdf (164 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Input
NAMUR- transmitter 0 ... 1 kHz (analysis of the NAMUR values)
Mechanical contact 0 ... 10 Hz (debounced input - Please note: low input bandwidth)
Active voltage 0 ... 1 kHz (12 V or 24 V)
Semiconductor switch 0 ... 1 kHz (such as transistor / optocoupler)
Relay output
Max. load AC 250 V / 2 A (cos phi = 1)
Max. load DC 50 V / 1 A (resistive load)
Cycles AC- load 2 A (cos phi = 1): ca. 110000
Cycles DC- load 1 A (resistive load): ca. 100000
Pulse duration 0,5 ... 5 s
Transistor output (optional)
Max. load DC 30V / 50mA
Pulse duration 0,05 ... 5 s (50% duty cycle at high frequency)
Supply
Voltage range 20 ... 253 V DC / 50 ... 253 V AC
Power consumption Max. 1,5 W / 2,6 VA
Housing
Dimensions (WxHxD) 18x110x134 mm
Type of protection IP 20
Connection method Detachable terminal clamp (2,5 mm² flex wire / 4 mm² one wire)
Bolting torque screw terminals 0,5 Nm
Weight 135 g
Manner of fastening DIN rail 35mm (EN 50022)
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
Electrical safety requirements
Product family standard EN 61010-1
Galvanic isolation, test voltages
Input / output 4 kV (1 min.)
Signal / supply unit 4 kV (1 min.)
Protection circuits
Input Electrical surge protection
Power supply Electrical surge and reverse current protection
Relay output No protection
Transistor output Electrical surge protection

Block and wiring diagram

AD-IU 214 GVC

Dimensions

AD-IU 214 GVC

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Cookie settings
made with ♡ by andres.media