AD-KSW 5 WG

Description

With the AD-KSW 5 WG split-core current transformers, currents of up to 5A AC can be measured without physical contact in combination with Adamczewski power transmitters or current transmitters. Thanks to the internal voltage limitation, the secondary cables do not carry any dangerous voltages even when the cables are open.

Application

Measurement of currents, power or energy in systems or buildings in combination with power measurement technology or current measurement technology from Adamczewski.

Specific characteristics

  • Non-contact measurement of currents
  • No disconnection of the main cable during installation
  • Non-critical secondary mA signals
  • Mounting on DIN rail
  • Voltage limitation of the secondary side when disconnecting the mA output signal

Business data

Order number
AD-KSW 5 WG-H Horizontal guidance of the conductor
AD-KSW 5 WG-V Vertical guidance of the conductor
Identifiers
Customs tariff number / country of origin 8504 31 29 / Deutschland

Information

Downloads
Data sheet pdf en-ksw5wg.pdf (137 kB)
Safety instructions pdf ad-safety-instructions.pdf (86 kB)

Technical specifications

Primary
Measuring range 0,01 ... 5 Arms
Max. continuously current 10 Arms
Frequency 10 Hz ... 50 kHz
Max. wire diameter 10 mm
Secundary
Open-circuit voltage 7,5 V AC
Max. burden 500 Ohm
Transfer characteristics
Turns ratio 3000 : 1
Current ratio 1,666 mA : 5 A
Phase error -1,5° +/-0,5° bei 5 Arms
Electrical safety requirements
Dielectric strength 2200 Vrms / 1 Minute
Max. working voltage 600 Vrms for insulated lines
Environment
Temperature -20 ... 50°C
Materials
Core material Ferrit
Housing split core current transformer PP, Fire class UL94V-O
Weight
Total ~ 150 g

Block and wiring diagram

AD-KSW 5 WG

Dimensions

AD-KSW 5 WG

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Cookie settings
made with ♡ by andres.media