AD-KV 100 GS, AD-KV 100 GS-O

Description

The contact protection pulse relay (switching amplifier) serves preferably the protection of weak transducer contacts or the amplification of binary transducer signals. The AD-KV 100 GS(o) provides the input pulse, temporarily amplified 1:1, at the output. At the same time it converts the prepared input signals to output pulses with constant, adjustable lengths (via trimmer at the front). Typical input signals are reed contacts, signal generator according to Namur (DIN EN 60947-5-6), TTL level, voltage signals or resistance changes. Heavy-duty and potential-free contacts are available at the output. The version AD-KI 100 GSO has wear-free transistor outputs, which are also galvanic separated via opto-coupler. Further, the device has an electronic wide-range power pack, which supplies the AD-KV 100 GS(o) energy-efficient from a wide supply voltage range.

AD-KV 100 GS, AD-KV 100 GS-O

Application

Pulse reception of water meter or flow monitors for metering the through-flow quantity. Amplification and contact protection of weak transducer signals (reed contacts, limit switches, etc.), sound signal transmission in control circuits. Sound amplifier for inductive and capacitive proximity switches according to Namur (DIN 19234).

Specific characteristics

  • support for all standard encoder types
  • via front-trimmer adjustable output pulse length
  • LEDs for signal display
  • two independent potential-free relay output (AD-AI 100 GS)
  • two independent semiconductor switches (AD-AI 100 GSO)
  • wide range power supply
  • narrow Design

Business data

Order number
AD-KV 100 GS-N With two independent relay outputs, Namur logic
AD-KV 100 GS-N-O With two independent semiconductor outputs, Namur logic
AD-KV 100 GS-K With two independent relay outputs, contact logic
AD-KV 100 GS-K-O With two independent semiconductor outputs, contact logic
Identifiers
Customs tariff number / country of origin 8538 90 91 / Deutschland

Information

Downloads
Data sheet pdf en-kv100gs.pdf (332 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Impulse input
Min. pulse width 2 ms
Namur supply voltage Ca. 8,2 V DC
Logic level for Namur signals Low < 1,2 mA ... High > 2,1 mA
Max. input voltage (active) 30 V DC
Logic level for active signals Low < 5 V ... High > 20 V
Type of contact Potential-free
Pulse processing
Output pulse length Output follows input 1:1
Relay outputs
Maximum switching load AC 250 V, 2 A
Maximum switching load DC 50 V, 2 A
Contact construction Potential-free changeover
Switching operations mechanical 10000000
At 230V/2A AC, cos(phi)=1 600000
At 230V/2A AC, cos(phi)=0,4 200000
At 24V/1 A DC 200000
Semiconductor outputs
Max switching voltage 30 V DC
Max. switching current 50 mA DC
Working voltage at pullup 10 ... 30 V DC
Internal pullup 5 kOhm
Supply
Voltage range AC 50 ... 253 V AC, 50/60 Hz
Nominal voltage AC 230 V AC
Voltage range DC 20 ... 253 V DC
Nominal voltage DC 24 V DC
Power consumption AC / DC 3 VA / 2W
Transmission behaviour
Temperature influence 100 ppm/K
Response time ~ 5 ms
Housing
Dimensions (WxHxD) 23x78x103 mm
Type of protection IP 20
Connection method Screw clamp
Terminals, wire cross section 2,5 mm² flex wire / 4 mm² one wire
Bolting torque terminals 0,5 Nm
Weight ~ 115 g
Manner of fastening 35 mm DIN rail 35mm
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1 1)
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Galvanic isolation, test voltages
Input / output 3,75 kV, 50 Hz (1 min.)
Signal / supply unit 4 kV, 50 Hz (1 min.)
Protection circuits
Input Electrical surge protection
Power supply Protection against over voltage, over temperature and reverse polarity
1) During checking, slight signal deviations are possible.

Block and wiring diagram

AD-KV 100 GS, AD-KV 100 GS-O

Dimensions

AD-KV 100 GS, AD-KV 100 GS-O

Circuit examples

AD-KV 100 GS, AD-KV 100 GS-O

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Cookie settings