AD-LU 625 GVF

Description

The digital power measuring transducer AD-LU 625 GVF measures all quantities of the three-phase network (current, voltage, energy, harmonics, phase angle, active power, reactive power, apparent power) and converts these measuring values onto two freely scalable analogue outputs. With the integral relay and transistor output, the switching of limiting values or the output of energy pulses is possible. The unit is therefore optimal suitable for integration in energy management systems. The current is measured via additionally available split-core current transformers. For measuring of high voltages, external transformers can be connected in series at any time. All measuring ranges and outputs can be freely parameterized. This can be carried out via the optional operating modul AD-VarioControl or via the programming software AD-Studio. The LEDs at the front signals the operating condition and the relay-status. The compact type of construction and the high performance ability with simultaneous low energy consumption allows usage in almost any application.

AD-LU 625 GVF

Application

Typical usage in plant, machines or energy management systems for balancing and determination of energy distribution.

Specific characteristics

  • Connection of 3 phases with neutral, any load
  • Current measurement via split-core current transformers up to 600 A
  • Measuring quantities: effective power, reactive power, apparent power, currents and voltages, frequency, power factor, harmonics, energy metering
  • current and voltage output
  • relay or transistor output
  • Counters for active power (consuption and infeed), reactive power (inductive and capacitive) and apparent power
  • 33 mm narrow housing with detachable terminal clamp
  • Operating module AD-VarioControl as an accessory

Business data

Order number
AD-LU 625 GVF
Accessory (optional)
AD-split core current transformer 5/50/100/200/400/600 A AC
Operating module AD-VarioControl
USB programming adapter AD-VarioPass
Configuration software AD-Studio
Identifiers
EClass 27210124
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-lu625gvf.pdf (503 kB)
Operation manual VarioControl pdf man-variocontrol-ad-en.pdf (1 MB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Current-inputs (I1...I3)
Measuring ranges 0 ... 0,05 A AC from split core current transformer
Max. measurable harmonic 40
Voltage-inputs (L1...L3)
Measuring range 10 ... 253 V AC
Input resistance > 1 MOhm
Output current
Output range 0/4 ... 20 mA
Max. load 400 Ohm
Resolution 11 Bit
Residual ripple 25 µAss
Output voltage
Output range 0/2 ... 10 V
Min. load 10 kOhm
Resolution 11 Bit
Residual ripple 20 mVss
Semiconductor output
Maximum switching load DC 30 V, 50 mA
Pulse length min ... max 50 ms ... 10000 ms
Relay output
Maximum switching load AC 250 V, 2 A
Maximum switching load DC 50 V, 2 A
Contact construction Potential-free changeover
Switching operations mechanical 1 * 107
At 230V/2A AC, cos(phi)=1 6 * 105
At 230V/2A AC, cos(phi)=0,4 2 * 105
At 24V/2A DC 2 * 105
Pulse length min ... max 500 ms ... 10000 ms
Supply
Voltage range AC 50 ... 253 V AC, 50/60 Hz
Nominal voltage AC / DC 230 V AC / 24 V DC
Voltage range DC 20 ... 253 V DC
Power consumption AC / DC 4,6 VA / 2,4 W
Power consumption with operating module AC / DC 4,8 VA / 2,6 W
Transmission behaviour
Basic accuracy < 0,5 % (class 0.5)
Temperature influence 80 ppm/K
Response time < 0,5 s
Housing
Dimensions (WxHxD) 33x110x134mm
With operating module (bxhxt) 33x110x138 mm
Type of protection IP 20
Connection method Detachable terminal clamp
Terminals, wire cross section 2,5 mm² flex wire / 4 mm² one wire
Bolting torque terminals 0,5 Nm
Skinning length 6 mm
Weight ~ 180 g
Manner of fastening 35 mm DIN rail 35mm
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1 1)
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
1) During checking, slight signal deviations are possible.
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Safety measurement EN 61010-2-030
Measurement category CAT III
Galvanic isolation, test voltages
Input to outputs / power-supply 4 kV, 50 Hz (1 min.)
Power-supply to outputs 3 kV, 50 Hz (1 min.)
Relay contacts to outputs 3 kV, 50 Hz (1 min.)
Protection circuits
Input Electrical surge protection
Power supply Protection against over-temperature, over-voltage and over-current
Analog outputs Electrical surge protection

Block and wiring diagram

AD-LU 625 GVF

Dimensions

AD-LU 625 GVF

Circuit examples

AD-LU 625 GVF

CAD / CAE Daten

Under "Generate CAD", select the desired CAD model for this product.
For this purpose, registration with our CAD database "PARTcommunity" is required.
The complete CAD product overview can be found at: adamczewski.partcommunity.com

AD-LU 625 GVF

Display and operating elements

On: LED for operating display in green
on - normal operation
flashing - Signal failure, signal outside range limits
A / Opto: LED for semiconductor switch
on - activated
B / rel: LED for relays
on - activated
AD-PC: Communication interface for configuration by a PC

Communication interface for VarioControl

Modbus Communication

The optional AD-VarioConnect operating module has an RS-485 interface. The data is transferred via the Modbus RTU protocol, the AD-VarioConnect operating module represents a Modbus slave. Communication takes place according to the master-slave procedure and starts with a request from the master, e.g. from a PLC or a PC. Each bus participant must have a unique address. If a slave detects that its address has been addressed by the master, the slave always sends an answer. The slaves never communicate with each other. They are also not able to start a communication with the master.
The Modbus master can read out the individual registers of the AD-LU 625 GVF via the addresses.
The default standard data format is 19200,e,8,1 with slave address 1. These settings can be changed via the AD-VarioConnect operating module.

Start address Number of registers Name Unit Data type read write

Measured values:
40202 1 digital output A 3 1 1
40203 1 digital output B 3 1 1
40204 1 digital output A LED 3 1 1
40205 1 digital output B LED 3 1 1
40501 2 active power total kW 7 1 0
40503 2 active power total L1 kW 7 1 0
40505 2 active power total L2 kW 7 1 0
40507 2 active power total L3 kW 7 1 0
40509 2 total reactive power kvar 7 1 0
40511 2 reactive power L1 kvar 7 1 0
40513 2 reactive power L2 kvar 7 1 0
40515 2 reactive power L3 kvar 7 1 0
40517 2 total apparent power kVA 7 1 0
40519 2 apparent power L1 kVA 7 1 0
40521 2 apparent power L2 kVA 7 1 0
40523 2 apparent power L3 kVA 7 1 0
40525 2 total power factor 7 1 0
40527 2 power factor in L1 7 1 0
40529 2 power factor in L2 7 1 0
40531 2 power factor in L3 7 1 0
40533 2 total active fundamental power kW 7 1 0
40535 2 active fundamental power L1 kW 7 1 0
40537 2 active fundamental power L2 kW 7 1 0
40539 2 active fundamental power L3 kW 7 1 0
40541 2 total active harmonic power kW 7 1 0
40543 2 active harmonic power L1 kW 7 1 0
40545 2 active harmonic power L2 kW 7 1 0
40547 2 active harmonic power L3 kW 7 1 0
40549 2 voltage L1 V 7 1 0
40551 2 voltage L2 V 7 1 0
40553 2 voltage L3 V 7 1 0
40555 2 current N line (calculated) A 7 1 0
40557 2 current in L1 A 7 1 0
40559 2 current in L2 A 7 1 0
40561 2 current in L3 A 7 1 0
40563 2 voltage peak L1 V 7 1 0
40565 2 voltage peak L2 V 7 1 0
40567 2 voltage peak L3 V 7 1 0
40569 2 current peak L1 A 7 1 0
40571 2 current peak L2 A 7 1 0
40573 2 current peak L3 A 7 1 0
40575 2 frequency Hz 7 1 0
40577 2 phase angle Phi L1 ° 7 1 0
40579 2 phase angle Phi L2 ° 7 1 0
40581 2 phase angle Phi L3 ° 7 1 0
40583 2 temperature °C 7 1 0
40585 2 phase angle Psi L1 ° 7 1 0
40587 2 phase angle Psi L2 ° 7 1 0
40589 2 phase angle Psi L3 ° 7 1 0
40801 2 output current mA 7 1 0
40803 2 output voltage V 7 1 0

Counter:
44003 2 counter kWh - consuption kWh 5 1 1
44005 2 counter kWh - infeed kWh 5 1 1
44007 2 counter kVarh - inductiv kVarh 5 1 1
44009 2 counter kVarh - capacitiv kVarh 5 1 1
44011 2 counter kVAh - apparent energy kVAh 5 1 1


Legend of the datatypes:
U08: 1 S08: 2 U16: 3 S16: 4 U32: 5 S32: 6 float: 7

Cookie settings
made with ♡ by andres.media