AD-MV 55 GX

Description

The digital temperature measuring converter of series AD-MV55 GX are freely programmable digital measuring transducer with RS485 interface. Device addresses from 1 to 99 can be set via the laterally accessible address switches. The input of all characteristics directly on the device, or use the configuration software "AD-Studio". The device fulfils all tasks of a universal measuring value recording through integral function modules such as selectable relay functions, simulation modus, free linearizing curves and a wide range of supply voltage. The operating voltage is indicated by a green LED. The data communication is signaled by a yellow LED. Invalid measurement signals outside the defined measuring range are detected. In this case, the green LED flashes. The power supply as well as the RS485 bus interface is possible via the rear DIN rail connector.

AD-MV 55 GX

Specific characteristics

  • Resistance thermometer inputs, types Pt/Ni 100, Pt/Ni 500, Pt/Ni 1000
  • Thermocouples inputs, types J, T, K, E, N, S, R, B, C or inputs a mV/T-characteristic curve. Selectable internal or external reference junction
  • A bipolar mV-Voltage input. Free linearizing curves possible.
  • Freely definable scaling of the quantity to be measured through stating range, decimal point position and unit from the list or defined unit.
  • Zoom function, expanded scale, linearizing, inverse modus.
  • Non-volatile saving of all set parameters.

Business data

Order number
AD-MV 55 GX
Identifiers
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-mv55gx.pdf (230 kB)
Tender text zip mv55gx.zip (7 kB)
STEP file step gx.step (3 MB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Resistance thermometer inputs Pt100, Pt500, Pt1000 to DIN EN 60751
Measuring range -200 ... +850 °C
Connection method 2-, 3- oder 4-wire system
Resolution 16 Bit
Accuracy 0,5 K
Smallest measuring spans 30 K
Max line resistance 1) 10 Ohm/cable
Sensor supply
Pt100 1 mA
Pt500, Pt1000 210 µA
1) With 2-conductor the line resistance comes as an offset into the measurement.
Resistance thermometer inputs Ni100, Ni500, Ni1000 to DIN EN 43760
Measuring range -60 ... +230 °C
Connection method 2-, 3- oder 4-wire system
Resolution 16 Bit
Accuracy 0,5 K
Smallest measuring spans 30 K
Max line resistance 1) 10 Ohm/cable
Sensor supply
Ni100 1 mA
Ni500, Ni1000 210 µA
1) With 2-conductor the line resistance comes as an offset into the measurement.
Thermocouples
Comparative place:
Internal Measurement with LM35 in the device connecting terminals
External Cold junction temperatureselectable by parameters
Resolution 16 Bit
Accuracy 0,2 % of measuring range
Measuring range type J -200 ... +1200 °C
To DIN EN 60584:
Measuring range type T -200 ... +400 °C
Measuring range type K -200 ... +1360 °C
Measuring range type E -200 ... +1000 °C
Measuring range type N -200 ... +1300 °C
Measuring range type S -40 ... +1760 °C
Measuring range type R -40 ... +1760 °C
Measuring range type B +400 ... +1800 °C
After standard ASTM E988:
Measuring range type C 0 ... +2320 °C
Smallest measuring spans 100 K
Voltage inputs
Measuring range -18 ... +18 mV
-36 ... +36 mV
-72 ... +72 mV
-144 ... +144 mV
Resolution 16 Bit
Accuracy 0,2 % of measuring range
Transmission behaviour
Sampling rate 1measure/s
Temperature influence +/-100 ppm/K of full scale
RS485-Bus
Software protocol Modbus-RTU
Data format 19200, e, 8, 1
Max. bus users 99
Bus termination 120 ohms both sides at the end
Max. length of bus 500 m (no spur lines)
Cable Twisted and shielded
LEDs
Green [On] Supply (blinking on error)
Yellow [D] RS485 Communication
Controls
Address switch 10 + 1
Supply
Supply voltage 18 ... 30 V DC
Max power consumption at 24V DC 300 mW
Housing
Dimensions (WxHxD) 6,2 x 92 x 101 mm³
Manner of fastening DIN rail mounting 35mm, EN 50022
Type of protection IP 20
Connection method Screw clamp
Bolting torque terminals 0,5 Nm
Wire cross section Max. 2,5 mm2
Weight ~ 70 g
Environmental conditions
Permissible ambient temperature -10 ... +50 °C
Storage and transport -10 ... +70 °C (no condensation)
EMC
Product family standard 2) EN 61326-1
Emission 3) EN 55011, CISPR11 Cl. A, Gr. 1
2) During electromagnetic disturbance minor changes in output signal are possible.
3) Warning:
This device is not intended to be used in residential areas and can not ensure adequate protection of radio reception in such environments.
Electrical safety requirements
Product family standard EN 61010-1
Galvanic isolation, test voltages
Signal / supply unit 1,5 kV, 50 Hz (1 min.)
Signal / RS485 bus Nogalvanic isolation

Block and wiring diagram

AD-MV 55 GX

Dimensions

AD-MV 55 GX