AD-MV 55 GX

Description

The digital temperature measuring converter of series AD-MV55 GX are freely programmable digital measuring transducer with RS485 interface. Device addresses from 1 to 99 can be set via the laterally accessible address switches. The input of all characteristics directly on the device, or use the configuration software "AD-Studio". The device fulfils all tasks of a universal measuring value recording through integral function modules such as selectable relay functions, simulation modus, free linearizing curves and a wide range of supply voltage. The operating voltage is indicated by a green LED. The data communication is signaled by a yellow LED. Invalid measurement signals outside the defined measuring range are detected. In this case, the green LED flashes. The power supply as well as the RS485 bus interface is possible via the rear DIN rail connector.

AD-MV 55 GX

Specific characteristics

  • Resistance thermometer inputs, types Pt/Ni 100, Pt/Ni 500, Pt/Ni 1000
  • Thermocouples inputs, types J, T, K, E, N, S, R, B, C or inputs a mV/T-characteristic curve. Selectable internal or external reference junction
  • A bipolar mV-Voltage input. Free linearizing curves possible.
  • Freely definable scaling of the quantity to be measured through stating range, decimal point position and unit from the list or defined unit.
  • Zoom function, expanded scale, linearizing, inverse modus.
  • Non-volatile saving of all set parameters.

Business data

Order number
AD-MV 55 GX
Accessory
Rail connector
(5-pin)
AD-GX-Connector
Identifiers
EClass 27210129
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-mv55gx.pdf (231 kB)
Tender text zip mv55gx.zip (7 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Resistance thermometer inputs Pt100, Pt500, Pt1000 to DIN EN 60751
Measuring range -200 ... +850 °C
Connection method 2-, 3- oder 4-wire system
Resolution 16 Bit
Accuracy 0,5 K
Smallest measuring spans 30 K
Max line resistance 1) 10 Ohm/cable
Sensor supply
Pt100 1 mA
Pt500, Pt1000 210 µA
1) With 2-conductor the line resistance comes as an offset into the measurement.
Resistance thermometer inputs Ni100, Ni500, Ni1000 to DIN EN 43760
Measuring range -60 ... +230 °C
Connection method 2-, 3- oder 4-wire system
Resolution 16 Bit
Accuracy 0,5 K
Smallest measuring spans 30 K
Max line resistance 1) 10 Ohm/cable
Sensor supply
Ni100 1 mA
Ni500, Ni1000 210 µA
1) With 2-conductor the line resistance comes as an offset into the measurement.
Thermocouples
Comparative place:
Internal Measurement with LM35 in the device connecting terminals
External Cold junction temperatureselectable by parameters
Resolution 16 Bit
Accuracy 0,2 % of measuring range
Measuring range type J -200 ... +1200 °C
To DIN EN 60584:
Measuring range type T -200 ... +400 °C
Measuring range type K -200 ... +1360 °C
Measuring range type E -200 ... +1000 °C
Measuring range type N -200 ... +1300 °C
Measuring range type S -40 ... +1760 °C
Measuring range type R -40 ... +1760 °C
Measuring range type B +400 ... +1800 °C
After standard ASTM E988:
Measuring range type C 0 ... +2320 °C
Smallest measuring spans 100 K
Voltage inputs
Measuring range -18 ... +18 mV
-36 ... +36 mV
-72 ... +72 mV
-144 ... +144 mV
Resolution 16 Bit
Accuracy 0,2 % of measuring range
Transmission behaviour
Sampling rate 1 measure/s
Temperature influence +/-100 ppm/K of full scale
RS485-Bus
Software protocol Modbus-RTU
Data format 19200, e, 8, 1
Max. bus users 99
Bus termination 120 ohms both sides at the end
Max. length of bus 500 m (no spur lines)
Cable Twisted and shielded
LEDs
Green [On] Supply (blinking on error)
Yellow [D] RS485 Communication
Controls
Address switch 10 + 1
Supply
Supply voltage 18 ... 30 V DC
Max power consumption at 24V DC 300 mW
Housing
Dimensions (WxHxD) 6,2 x 92 x 101 mm³
Manner of fastening DIN rail mounting 35mm, EN 50022
Type of protection IP 20
Connection method Screw clamp
Bolting torque terminals 0,5 Nm
Wire cross section Max. 2,5 mm2
Weight ~ 70 g
Environmental conditions
Permissible ambient temperature -10 ... +50 °C
Storage and transport -10 ... +70 °C (no condensation)
EMC
Product family standard 2) EN 61326-1
Emission 3) EN 55011, CISPR11 Cl. A, Gr. 1
2) During electromagnetic disturbance minor changes in output signal are possible.
3) Warning:
This device is not intended to be used in residential areas and can not ensure adequate protection of radio reception in such environments.
Electrical safety requirements
Product family standard EN 61010-1
Galvanic isolation, test voltages
Signal / supply unit 1,5 kV, 50 Hz (1 min.)
Signal / RS485 bus Nogalvanic isolation

Block and wiring diagram

AD-MV 55 GX

Dimensions

AD-MV 55 GX

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Modbus Communication

The AD-MV 55 GX has an RS485 bus interface on which the Modbus RTU protocol is used. About this bus interface all measured data of the device can be read. The preset standard data format is 19200,e,8,1. Adaptation to a different data format is possible at any time. The bus address (1...99) is set to the side-mounted rotary switches. The address 0 is not permitted for the bus operation. However, on this zero position the device only via the standard data format (19200, e, 8.1) accessible. The position 0 thus represents a service position, the example can be used during parameterization error.

The AD-MV 55 GX supports two Modbus functions. These are the functions "Read Holding Registers" (0x03) and "Write Holding Registers" (0x10). With the "Read Holding Registers" function data can be read from the device and written with "Write Holding Registers" data. The individual register width is 16 bits. Please see the Modbus specification for detailed explanations of the Modbus communication. This is online available for free, but can also be purchased from the Adamczewski homepage.

The following Modbus data are accessible via the RS485 bus:

Observations

Start address Reg. number Name Unit Datatype [Code] = Value read write
40113 1 signal status keine U16 0 / 1 / 2 / 4 yes no
40851 2 signal value °C / mV float ####,# yes no
40852 6 scale unit °C / mV string unit yes no
40811 2 terminal temperature °C float ##,#### yes no


Parameters
Start address Reg. number Name Unit Datatype [Code] = Value read write
43101 2 filter value numeric float seconds yes yes
43001 1 signal type list U16 [0]=RTD; [1]= TC; [2]=mV yes yes
43002 1 RTD type list U16 RTD-Liste yes yes
43003 1 RTD connectivity list U16 2-3-4-Leiter yes yes
43201 2 range begin Pt100 °C float -200...+850 yes yes
43301 2 range end Pt100 °C float -200...+850 yes yes
43202 2 range begin Pt500 °C float -200...+850 yes yes
43302 2 range end Pt500 °C float -200...+850 yes yes
43203 2 range begin Pt1000 °C float -200...+850 yes yes
43303 2 range end Pt1000 °C float -200...+850 yes yes
43204 2 range begin Ni100 °C float -60...+230 yes yes
43304 2 range end Ni100 °C float -60...+230 yes yes
43205 2 range begin Ni500 °C float -60...+230 yes yes
43305 2 range end Ni500 °C float -60...+230 yes yes
43206 2 range begin Ni1000 °C float -60...+230 yes yes
43306 2 range end Ni1000 °C float -60...+230 yes yes
43207 2 range begin R/T °C float -200...1500 yes yes
43307 2 range end R/T °C float -200...1500 yes yes
43401 2 R/T characteristic X1 Ohm float 0...4000 yes yes
43425 2 R/T characteristic Y1 °C float -200...1500 yes yes
43400 + n 2 R/T characteristic Xn Ohm float 0...4000 yes yes
43424 + n 2 R/T characteristic Yn °C float -200...1500 yes yes
43424 2 R/T characteristic X24 Ohm float 0...4000 yes yes
43448 2 R/T characteristic Y24 °C float -200...1500 yes yes
43004 1 TC type list U16 TC-Liste yes yes
43005 1 junction list U16 [0]=int.; [1]=ext. yes yes
43102 2 junction temperature °C float 0...100 yes yes
43208 2 range begin Typ J °C float -200...+1200 yes yes
43308 2 range end Typ J °C float -200...+1200 yes yes
43209 2 range begin Typ T °C float -200...+400 yes yes
43309 2 range end Typ T °C float -200...+400 yes yes
43210 2 range begin Typ K °C float -200...+1360 yes yes
43310 2 range end Typ K °C float -200...+1360 yes yes
43211 2 range begin Typ E °C float -200...+1000 yes yes
43311 2 range end Typ E °C float -200...+1000 yes yes
43212 2 range begin Typ N °C float -200...+1300 yes yes
43312 2 range end Typ N °C float -200...+1300 yes yes
43213 2 range begin Typ S °C float -40...+1760 yes yes
43313 2 range end Typ S °C float -40...+1760 yes yes
43214 2 range begin Typ R °C float -40...+1760 yes yes
43314 2 range end Typ R °C float -40...+1760 yes yes
43215 2 range begin Typ B °C float +400...+1800 yes yes
43315 2 range end Typ B °C float +400...+1800 yes yes
43216 2 range begin Typ C °C float 0...+2320 yes yes
43316 2 range end Typ C °C float 0...+2320 yes yes
43217 2 range begin U/T °C float -200...+2500 yes yes
43317 2 range end U/T °C float -200...+2500 yes yes
43449 2 U/T characteristic X1 mV float -144...144 yes yes
43473 2 U/T characteristic Y1 °C float -200...1500 yes yes
43448 + n 2 U/T characteristic Xn mV float -144...144 yes yes
43472 + n 2 U/T characteristic Yn °C float -200...1500 yes yes
43472 2 U/T characteristic X24 mV float -144...144 yes yes
43496 2 U/T characteristic Y24 °C float -200...1500 yes yes
42997 1 baud rate index U16 see list below yes yes
42998 1 parity U16 [0]=even; [1]=odd; [2]=no yes yes


Coding baudrate list
Index 0 1 2 3 4 5 6 7 8 9
baud 2400 4800 9600 14400 19200 28800 38400 57600 76800 115200