AD-TV 588 GVD

Description

The AD-TV 588 GVD is used for measuring the rms value of alternating current via a built-in current transformer up to 5A or via an external clamp on / split core current transformer up to 600A. The detected current is outputted as a galvanically isolated standard current signal in the range 0 to 20 mA and as a standard voltage signal in the range 0 to 10 volts. An additional relay output can indicate a limit value or a window. All parameters such as range, output range, relay functions, limiting values, etc. can be freely set via the configuration software.

AD-TV 588 GVD

Application

Measuring the current of single-phase loads up to 600A. Monitoring of current consumption to certain limits with hysteresis threshold by limit function. Monitoring a certain range of the current consumption by window function.

Specific characteristics

  • Detection of the rms value of alternating currents up to 600A
  • Current and voltage output can be used simultaneously
  • Relay output, NO
  • Wide range power supply. Supply with 24V DC or 230V AC available
  • External clamp on/split core current transformers as accessory available
  • Configuration information, such as limits, input current, etc. can be adjusted by the customer via configuration software or be specified when ordering
  • Operating module as an accessory

Business data

Order number
AC Isolation Amplifier AD-TV 588 GVD
Accessory (optional)
Split core current transformer AD-KSW 5/50/100/200/400/600 A AC
Display/control module AD-VarioControl, VarioConnect
USB programming adapter AD-VarioPass
Configuration software AD-Studio
Identifiers
EClass 27210123
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-tv588gvd.pdf (204 kB)
Operation manual VarioControl pdf man-variocontrol-ad-en.pdf (1 MB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Input current directly
Measuring range 1 A 0 ... 1 A AC
Measuring range 5 A 0 ... 5 A AC
Remark DO NOT CONFUSE THE INPUT OF THE CLAMP ON CURRENT TRANSFORMER.
Current input via Clamp on Current Transformer
Measuring range, Re, Terminals 0 ... 1,66 mA AC, 200 Ohm, 5/6
Measuring range, Re, Terminals 0 ... 16,6 mA AC, 20 Ohm, 6/7
Measuring range, Re, Terminals 0 ... 33,3 mA AC, 10 Ohm, 7/8
(alle AD-KSW XXX)
Measuring range, Re, Terminals 0 ... 66,6 mA AC, 5 Ohm, 8/1
All current inputs
Rated frequency 50 Hz
Frequency range 40 ... 400 Hz
Sampling 2 kHz
All signal outputs
Simultaneous use Yes. Minus (terminals 10/12) may not be connected.
Bit width D/A converter (PWM) 11 Bit
Output current
Maximum output range 0 ... 20 mA
Resolution ~10 uA
Max. burden 500 Ohm
Output voltage
Maximum output range 0 ... 10 V
Resolution ~5 mV
Min. burden 1 kOhm
Relay output
Maximum switching load AC 250 V, 2 A
Maximum switching load DC 50 V, 2 A
Contact construction Closing contact
Switching operations mechanical 10.000.000
At 230V/2A AC, cos(phi)=1 600.000
At 230V/2A AC, cos(phi)=0,4 200.000
At 24V/1 A DC 200.000
Transmission behaviour
Maximum linearity error 0,5 % of full scale
Rise time 0..90% 200 ms
Temperature influence +/- 100 ppm/K
Supply
Voltage range AC 50 ... 253 V AC, 50/60 Hz
Nominal voltage AC 230 V AC
Voltage range DC 20 ... 253 V DC
Nominal voltage DC 24 V DC
Power consumption AC / DC 3 VA / 1,5 W
Housing
Dimensions (WxHxD) 23x110x134 mm
With operating module (bxhxt) 23x110x138 mm
Manner of fastening DIN rail 35mm (EN 50022)
Type of protection IP 20
Connector cross section Max. 2,5 mm²
Bolting torque screw terminals 0,5 Nm
Weight ~120 g
Environmental conditions
Operation -10 ... 50 °C
Storage, transport -10 ... 60 °C
EMC
Product family standard EN 61326-1 1)
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
Electrical safety requirements
Product family standard EN 61010-1
Galvanic isolation, test voltages
Input/output 4 kV, 1 min
Input, output/supply 4 kV, 1 min
Notifications
Operation Green LED. Blinks when signal outside range
Relay Red LED. Lit when relay is energized
1)During electromagnetic disturbance minor changes in output signal are possible.

Block and wiring diagram

AD-TV 588 GVD

Dimensions

AD-TV 588 GVD

CAD / CAE Daten

Under "Generate CAD", select the desired CAD model for this product.
For this purpose, registration with our CAD database "PARTcommunity" is required.
The complete CAD product overview can be found at: adamczewski.partcommunity.com

AD-TV 588 GVD

Display and operating elements



On: LED for operating display in green
on - normal operation
flashing - Signal failure, signal outside range limits
Rel: LED for relay in red
on - relay activated

AD-PC: Communication interface for configuration by a PC

Communication interface for VarioControl

Modbus/RTU Communication

The optional AD-VarioConnect operating module is required for communication via Modbus/RTU. It has an RS-485 interface. The data format is 19200,e,8,1. The slave address is 1. These settings can be changed using the AD-VarioConnect operating module. The following data can be communicated.

Start address Number of registers Name Unit Data type read write
40701 2 Scaled input A AC float 1 0
40801 2 Output signal current mA float 1 1
40803 2 Output signal voltage V float 1 1

Use of the Adamczewski AD-KSW XXX folding current transformers

All AD-KSW XXX folding current transformers provide an output current of 33.33 mA regardless of the input current. Therefore, when using these transformers, ALWAYS use input terminals 7/8.

Cookie settings
made with ♡ by andres.media