AD-TV 588 GVD (V1)

Description

The AD-TV 588 GVD is used for measuring the rms value of alternating current by a built-in current transformer up to 5A or by an external clamp on / split core current transformer up to 600A. The detected current is output as a galvanically isolated standard current signal in the range 0 to 20 mA and a standard voltage signal in the range 0 to 10 volts. An additional relay output can indicate a limit value or a window. All parameters such as range, output range, relay functions, limits, etc. are freely set by the configuration software.

AD-TV 588 GVD (V1)

Application

Measuring the current of single-phase loads up to 600A. Monitoring of current consumption to certain limits with hysteresis threshold by limit function. Monitoring a certain range of the current consumption by window function.

Specific characteristics

  • Detection of the rms value of alternating currents up to 600A.
  • Current and voltage output can be used simultaneously.
  • Relay output, NO.
  • Wide range power supply. Supply with 24V DC or 230V AC available.
  • External clamp on/split core current transformers as accessory available.
  • Configuration information, such as limits, input current, etc. can be adjusted by the customer via configuration software or be specified when ordering.

Business data

Order number
AC Isolation Amplifier AD-TV 588 GVD
Accessory
Configuration software AD-Studio USB
Split core current transformer 5A SWL-5A
25x33x41mm, 60g
Diameter max. 10mm
Split core current transformer 50A SWL-50A
26x23x48mm, 45g
Diameter max. 10mm
Split core current transformer 100A SWL-100A
31x30x54mm, 85g
Diameter max. 16mm
Split core current transformer 200A SWL-200A
36x45x76mm, 190g
Diameter max. 24mm
Split core current transformer 400A SWL-400A
60x40x80mm, 310g
Diameter max. 35mm
Split core current transformer 600A SWL-600A
60x40x80mm, 350g
Diameter max. 35mm
All Clamp on Current Transformers Accuracy 1%
open-circuit voltage max. 7,5V

Information

Downloads
Tender text zip tv588gvd.zip (15 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Input current directly
Measuring range 1 A 0 ... 1 A AC
Measuring range 5 A 0 ... 5 A AC
Remark DO NOT CONFUSE THE INPUT OF THE CLAMP ON CURRENT TRANSFORMER.
Current input via Clamp on Current Transformer
Measuring range 5 A 0 ... 1,66 mA AC
Converter type 5 A SWL-5A
Input resistance 5 A 200 Ohm
Measuring range 50 A 0 ... 16,6 mA AC
Converter type 50 A SWL-50A
Input resistance 50 A 20 Ohm
Measuring range 100 A 0 ... 33,3 mA AC
Converter type 100 A SWL-100A
Input resistance 100 A 10 Ohm
Measuring range 200/400/600A 0 ... 66,6 mA AC
Converter type 200 A SWL-200A
Converter type 400 A SWL-400A
Converter type 600 A SWL-600A
Input resistance 200/400/600A 5 Ohm
All current inputs
Rated frequency 50 Hz
Frequency range 40 ... 400 Hz
Sampling 2 kHz
All signal outputs
Simultaneous use Yes. Minus (terminals 10/12) may not be connected.
Bit width D/A converter (PWM) 11 Bit
Output current
Maximum output range 0 ... 20 mA
Resolution ~10 uA
Max. burden 500 Ohm
Output voltage
Maximum output range 0 ... 10 V
Resolution ~5 mV
Min. burden 1 kOhm
Relay output
Maximum switching load AC 250 V, 2 A
Maximum switching load DC 50 V, 2 A
Contact construction Closing contact
Switching operations mechanical 10.000.000
at 230V/2A AC, cos(phi)=1 600.000
at 230V/2A AC, cos(phi)=0,4 200.000
at 24V/1 A DC 200.000
Transmission behaviour
Maximum linearity error 0,5 % of full scale
Rise time 0..90% 200 ms
Temperature influence +/- 100 ppm/K
Supply
DC 20 ... 253 V DC, max. 1,5W
AC 50 ... 253 V AC, max. 3 VA
Housing
Manner of fastening DIN rail 35mm (EN 50022)
Type of protection IP 20
Connector cross section Max. 2,5 mm²
Bolting torque screw terminals 0,5 Nm
Weight ~120 g
Environmental conditions
Operation 0 ... 50 °C
Storage, transport -10 ... 60 °C
EMC
Product family standard EN 61326 1)
Emitted interference EN 55011, CISPR11 Cl. B
Electrical safety requirements
Product family standard EN 61010-1
Galvanic isolation, test voltages
Input/output 4 kV, 1 min
Input, output/supply 4 kV, 1 min
Notifications
Operation Green LED. Blinks when signal outside range
Relay Red LED. Lit when relay is energized
1)During electromagnetic disturbance minor changes in output signal are possible.

Block and wiring diagram

AD-TV 588 GVD (V1)

Dimensions

AD-TV 588 GVD (V1)

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Cookie settings
made with ♡ by andres.media