AD-UW 60 GT

Description

The three-phase voltage monitor AD-UW 60 GT monitors all three phases in the three-phase system for overvoltage, undervoltage, phase sequence and phase symmetry. If one or more faults occur, the quiescent current relay will fail. The state of the three phases and the error state is indicated by LEDs. The device is powered by the measuring voltage, therefore the wiring of a separate supply is eliminated. The switching points for overvoltage, undervoltage and switching delay can be set quickly via separate trimmers.

AD-UW 60 GT

Application

AC motors, Overhead cranes, Trolleys, Goods lifts, Conveyor belts

Specific characteristics

  • Setting the limits for undervoltage, overvoltage and switching delay via the front panel
  • Check all relevant sizes for a wide variety of purposes
  • Display of the phase voltages by green LEDs
  • Display of the relay by orange LED
  • No separate power supply necessary therefore less wiring effort
  • Relay is energized in the good range

Business data

Order number
AD-UW 60 GT
Identifiers
EClass 27371803
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-uw60gt.pdf (210 kB)
Tender text zip uw60gt.zip (10 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Voltage inputs/supply
Nominal voltage 230 V AC, 50 Hz
Connection method 3 phases + neutral conductor
Auxiliary voltage All three phases
Measurement and supply range 150 ... 253 V AC
Max. power consumption 4 VA
Setting ranges
Undervoltage 170 ... 229 V AC
Overvoltage 231 ... 250 V AC
Delay 0,1 ... 10 s
Response values
Asymmetry 10 % of nominal voltage
Hysteresis 10 % overvoltage - undervoltage
Phase loss ~ 10 % der Nennspannung
Timing
Start delay 1 s
Sampling period 50 ms
Notifications
L1, L2, L3 (green) On: Voltage OK
Blinking: Error, Delay is running
Off: Error
Relais (orange) On: Relay tightened, everything OK
Blinking: Relay dropped, error
Relay output
Maximum switching load AC 250 V, 2 A
Maximum switching load DC 50 V, 2 A
Contact construction Potential-free changeover
Galvanic isolation, test voltages
Mains side to relay output 4 kV, 50 Hz (1 min.)
Housing
Terminals, wire cross section 2,5 mm² flex wire / 4 mm² one wire
Type of protection IP 20
Connection method Screw clamp
Bolting torque terminals 0,6 Nm
Weight ~ 150 g
Manner of fastening 35 mm DIN rail 35mm
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category III
Pollution degree 2
Safety measurement EN 61010-2-030
Measurement category CAT III
EMC
Product family standard EN 61326-1 1)
Emitted interference EN 55011, CISPR11 Cl. A 2), Gr. 1
1) During checking, slight signal deviations are possible.
2)Warning: This device is not intended to be used in residential areas and can not ensure adequate protection of radio communications in such environments

Block and wiring diagram

AD-UW 60 GT

Dimensions

AD-UW 60 GT

Circuit examples

AD-UW 60 GT

CAD / CAE Daten

Under "Generate CAD", select the desired CAD model for this product.
For this purpose, registration with our CAD database "PARTcommunity" is required.
The complete CAD product overview can be found at: adamczewski.partcommunity.com

AD-UW 60 GT

Display and operating elements

1 Status voltage in L1
2 Status voltage in L2
3 Status voltage in L3
4 Relay state
5 Setting for overvoltage
6 Setting for undervoltage
7 Setting for switching delay
Cookie settings
made with ♡ by andres.media