AD-LU 451 GT-PN

Description

The digital power converter AD-LU 451 GT-PN measures all values of the three-phase power grid such as current, voltage, energy, active, reactive, apparent power and frequency and makes this data available via a fieldbus. The device is therefore ideally suited for integration into energy management systems. The AD-LU 451 GT-PN has a ProfiNet interface with a 2-port switch for direct looping to the next device. 3- or 4-wire networks can be measured. 4-wire networks may have balanced or unbalanced load. 3-wire networks must have balanced load. The integrated wide-range power supply enables operation over a wide supply voltage range. The current measurement takes place via external split-core current transformers, which can be mounted on the wire to be measured without cutting. For the measurement of higher voltages, external converters can be connected at any time. LEDs on the front panel signal the operating state and the data traffic. The compact design and the high performance combined with low energy consumption allow it to be used in almost any application. In addition, the device has a front-sided RS485 interface to which, for example, the TFT display AD-MM 400 can be connected. Thus, without any great effort, all measured values can be displayed.

AD-LU 451 GT-PN

Application

Measurement and monitoring of all electrical characteristics in electrical systems. Detection of load profiles for energy management systems, e.g. ISO 50001. Recording the energy consumption of individual consumers. Monitoring of voltage quality variables, e.g. Harmonics.
Attention: This is a Class A product according to EN 55011. Additional EMC actions may be necessary when used in small businesses or in residential areas.

Specific characteristics

  • Connection of 4-wire systems of any load
  • Measurement of currents, voltages, power, power factors, frequency, harmonics
  • Low power loss during current measurement thanks to external spli-core transformers
  • Counters for applied and feedback energies
  • Counters for inductive and capacitive reactive power
  • Fieldbus interface for PROFINET
  • RS485 interface for connecting a TFT display
  • Supply via wide-range power supply
  • Configuration of current and voltage transformers only via Profinet

Business data

Order number
AD-LU 451 GT-PN PROFINET
Accessory
AD-MM 400 FE TFT display for front panel installation
AD-MM 500 FE TFT display for front panel installation including data logging
AD-KSW 50 50 A split-core-transformer
AD-KSW 100 100 A split-core-transformer
AD-KSW 200 200 A split-core-transformer
AD-KSW 400 400 A split-core-transformer
AD-KSW 600 600 A split-core-transformer

Information

Downloads
Data sheet pdf en-lu451gt-pn.pdf (806 kB)
Tender text zip lu451gt-pn.zip (9 kB)
Basic knowledge of power and energy measurement technology pdf lu-grundbegriffe.pdf
Safety instructions pdf ad-safety-instructions.pdf (86 kB)

Technical specifications

Current-inputs (I1...I3)
Measuring ranges 0 ... 33,3 mA (over split-core-transformer)
Input resistance Ca. 10 Ohm
Max. measurable harmonic 40
Voltage-inputs (L1...L3)
Measuring range 0 ... 253 V AC
Input resistance Ca. 970 kOhm
PROFINET
Ethernet 2 Port Switch
Protocol specification PROFINET IO
Default IP-address 0.0.0.0
RS485-Bus
Software protocol Modbus-RTU
Data format 19200, e, 8, 1
Max. bus users 99
Bus termination 120 ohms both sides at the end
Max. length of bus 500 m (no spur lines)
Cable Twisted and shielded
Address setting BCD-switches 00...99
Broadcast adress 0
Supply
Voltage range AC 50 ... 253 V AC, 50/60 Hz
Voltage range DC 20 ... 253 V DC
Nominal voltage AC/DC 230 V AC / 24 V DC
Input power AC/DC Max. 4 VA / 3 W
Measure
Basic accuracy <= 0,5 % (class 0.5)
Temperature influence 80 ppm/K
Sampling interval 200 ms
Housing
Dimensions (WxHxD) 105x90x60 mm
Type of protection IP 20
Connection method Screw clamp
Terminals, wire cross section 2,5 mm² flex wire / 4 mm² one wire
Bolting torque terminals 0,6 Nm
Weight ~ 400g
Manner of fastening 35 mm DIN rail 35mm
Skinning length 6mm
Environmental conditions
Ambient temperature -10 ... 60 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1 1)
Emitted interference EN 55011, CISPR11 Cl. A, Gr. 1
1) During checking, slight signal deviations are possible.
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Safety measurement EN 61010-2-030
Measurement category CAT III
Galvanic isolation, test voltages
Grid side zu bus 4 kV, 50 Hz (1 min.)
Grid side to control elements 4 kV, 50 Hz (1 min.)

Block and wiring diagram

AD-LU 451 GT-PN

Dimensions

AD-LU 451 GT-PN

Circuit examples

AD-LU 451 GT-PN

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Explanations:

PROFINET: NS-Led (Netzwork Status):
The NS-LED signals the network status.

LED Status: Description: Comments
off Offline - no Power
- no connection with IO-Controller
green Online RUN - connection with IO-Controller established
- IO-Controller in RUN Status
green - 1 flash Online STOP - connection with IO-Controller established
- IO-Controller in STOP Status
- IO-data bad
- IRT synchronization not finished
green - blinking link mode - Uses by engineering tools to identify the
   node on the network
red fatal event - Major internal error
red - 1 flash station name error - Station name not set
red - 2 flash IP-Address error - IP-address not set
red - 3 flash configuration error - Expected identification differs from
   real identification


PROFINET: MS-Led (Modul Status):
The MS-LED signals the status of the ProfiNet module in the power meter.

LED Status: Description: Comments
off not initialized - Nor power or module in "SETUP" or
   "NW-INIT" state
green normal operation - Modul has shifted from "NW-INIT" state
green - 1 flash diagnostic event - diagnostic event present
red exception error or fatal event - Device in state EXCEPTION or major
   internal error
alternating red/green firmwareupdate - Do not power off the modul
- turning the module off during this phase
   could cause permanent damage

Modbus-Data (RS485-bus)


Messwerte:

address count register name unit type read write
40801 2 TOTAL_ACTIVE_POWER kW float 1 0
40803 2 PHASE_A_ACTIVE_POWER kW float 1 0
40805 2 PHASE_B_ACTIVE_POWER kW float 1 0
40807 2 PHASE_C_ACTIVE_POWER kW float 1 0
40809 2 TOTAL_REACTIVE_POWER kvar float 1 0
40811 2 PHASE_A_REACTIVE_POWER kvar float 1 0
40813 2 PHASE_B_REACTIVE_POWER kvar float 1 0
40815 2 PHASE_C_REACTIVE_POWER kvar float 1 0
40817 2 TOTAL_APPARENT_POWER kVA float 1 0
40819 2 PHASE_A_APPARENT_POWER kVA float 1 0
40821 2 PHASE_B_APPARENT_POWER kVA float 1 0
40823 2 PHASE_C_APPARENT_POWER kVA float 1 0
40825 2 TOTAL_POWER_FACTOR float 1 0
40827 2 PHASE_A_POWER_FACTOR float 1 0
40829 2 PHASE_B_POWER_FACTOR float 1 0
40831 2 PHASE_C_POWER_FACTOR float 1 0
40833 2 TOTAL_ACTIVE_FUNDAMENTAL_POWER kW float 1 0
40835 2 PHASE_A_ACTIVE_FUNDAMENTAL_POWER kW float 1 0
40837 2 PHASE_B_ACTIVE_FUNDAMENTAL_POWER kW float 1 0
40839 2 PHASE_C_ACTIVE_FUNDAMENTAL_POWER kW float 1 0
40841 2 TOTAL_ACTIVE_HARMONIC_POWER kW float 1 0
40843 2 PHASE_A_ACTIVE_HARMONIC_POWER kW float 1 0
40845 2 PHASE_B_ACTIVE_HARMONIC_POWER kW float 1 0
40847 2 PHASE_C_ACTIVE_HARMONIC_POWER kW float 1 0
40849 2 PHASE_A_VOLTAGE_RMS V float 1 0
40851 2 PHASE_B_VOLTAGE_RMS V float 1 0
40853 2 PHASE_C_VOLTAGE_RMS V float 1 0
40855 2 N_LINE_CALCULATED_CURRENT_RMS A float 1 0
40857 2 PHASE_A_CURRENT_RMS A float 1 0
40859 2 PHASE_B_CURRENT_RMS A float 1 0
40861 2 PHASE_C_CURRENT_RMS A float 1 0
40863 2 CHANNEL_A_VOLTAGE_PEAK V float 1 0
40865 2 CHANNEL_B_VOLTAGE_PEAK V float 1 0
40867 2 CHANNEL_C_VOLTAGE_PEAK V float 1 0
40869 2 CHANNEL_A_CURRENT_PEAK A float 1 0
40871 2 CHANNEL_B_CURRENT_PEAK A float 1 0
40873 2 CHANNEL_C_CURRENT_PEAK A float 1 0
40875 2 FREQUENCY Hz float 1 0
40877 2 PHASE_A_MEAN_PHASE_ANGLE ° float 1 0
40879 2 PHASE_B_MEAN_PHASE_ANGLE ° float 1 0
40881 2 PHASE_C_MEAN_PHASE_ANGLE ° float 1 0
40883 2 PHASE_A_VOLTAGE_PHASE_ANGLE ° float 1 0
40885 2 PHASE_B_VOLTAGE_PHASE_ANGLE ° float 1 0
40887 2 PHASE_C_VOLTAGE_PHASE_ANGLE ° float 1 0
40889 2 MEASURED_TEMPERATURE °C float 1 0
40891 2 PHASE_AB_VOLTAGE_RMS V float 1 0
40893 2 PHASE_BC_VOLTAGE_RMS V float 1 0
40895 2 PHASE_CA_VOLTAGE_RMS V float 1 0


Zähler:
address count register name unit type read write
44009 2 ENERGY_KWH_TOTAL_CONSUMPTION kWh U32 1 1
44011 2 ENERGY_KWH_TOTAL_INFEED kWh U32 1 1
44013 2 ENERGY_KVARH_TOTAL_INDUCTIVE kVarh U32 1 1
44015 2 ENERGY_KVARH_TOTAL_CAPACITIVE kVarh U32 1 1
44017 2 ENERGY_KVAH_TOTAL kVAh U32 1 1
44019 2 WORKING HOURS h U32 1 1
44021 2 LOAD HOURS h U32 1 1