AD-SMV 400 GVC

Description

The sum data amplifier adds up or subtracts up to 4 singly rateable input signals and converts these to a sum proportional or difference proportional output signal. As input signals, currents up to 20 mA or voltages up to 10 V (also bipolar) are possible. The inputs are galvanic separated from the auxiliary voltage and the outputs. The two analogue outputs current (max. 20mA) and voltage (max. 10V) can be utilised simultaneously. The device can be configured with the optional configuration software AD-Studio via the interface AD-PC. However, this can also be carried out at the works according to customer data.

AD-SMV 400 GVC

Application

Analogue summing/subtraction of single measurable variables such as through flows, outputs or quantities.

Business data

Order number
AD-SMV 400 GVC-I 4 Current inputs
AD-SMV 400 GVC-U 4 voltage inputs
Identifiers
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Technical specifications

Current inputs
Measuring range 1) -20 ... + 20 mA
Number 4
Input resistance 60 Ohm
Voltage inputs
Measuring range 1) -10 ... + 10 V
Number 4
Input resistance 1 MOhm
1) Please specify current or voltage inputs when ordering. A galvanic coupling is to be excluded.
Output current
Max. output range 0 ... 20,4 mA
Max. burden 500 Ohm
Residual ripple 20 µAss
Output voltage
Max. output range 0 ... 10,2 V
Min. burden 5 kOhm
Residual ripple 10 mVss
Resolution
Input 13 bit
Output 10 bit
Transmission behaviour
Basic accuracy 0,2 % of full scale
Temperature influence < 100 ppm/K of full scale
Rise time 100 ms (output auf 90 %)
Supply
Voltage range AC 50 ... 253 V AC, 50/60 Hz
Nominal voltage AC 230 V AC
Voltage range DC 20 ... 253 V DC
Nominal voltage DC 24 V DC
Power consumption AC / DC 2,6 VA / 1,2 W
Housing
Manner of fastening DIN rail 35mm (EN 50022)
Type of protection IP 20
Connector cross section Max. 2,5 mm²
Weight ~ 140 g
Environmental conditions
Ambient temperature -10 ... 60 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard 2) EN 61326-1
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
2) During electromagnetic disturbance minor changes in output signal are possible.
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Galvanic isolation, test voltages
Input/output 2,5 kV (1 min)
Signal/auxiliary voltage 3 kV (1 min)
Protective systems
Input/output Over voltage and over current
Power supply Over voltage, over current and over temperature

Block and wiring diagram

AD-SMV 400 GVC

Dimensions

AD-SMV 400 GVC

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Cookie settings
made with ♡ by andres.media