AD-SWT 50 SO-TRMS, AD-SWT 100 SO-TRMS, AD-SWT 200 SO

Description

The SWT-TRMS series of devices (AD-SWT 50 SO-TRMS, AD-SWT 100 SO-TRMS and AD-SWT 200 SO-TRMS) serves the measuring of large AC currents and simultaneous conversion to 4...20 mA transmitter signal. Because of the RMS measurement, the current consumption of non-linear consumers can be measured. Even strong distortions of the sinusoidal signal are easily measurable through the high sampling rate. The devices are designed in two-wire technology and can be operated in a wide range of voltages. Dependent on the amount of the primary current, the devices sink a proportional 4...20 mA signal from the connected supply voltage. Due to the integral protection against polarization error and over-voltage, the transmitter are also protected against erroneous applications or transient over-voltages. The housing is designed in external clamp-on transformer format and therefore can be easily integrated into existing units.

AD-SWT 50 SO-TRMS, AD-SWT 100 SO-TRMS, AD-SWT 200 SO

Application

Measurement of large alternating currents, of linear or non-linear loads.

Attention: when fitting, it must be ensured that the ferrite surfaces of the SWT are free from dirt or fat residues through contact. Otherwise measuring value deviations or even error measurings are possible.

Specific characteristics

  • Clamp-on transformer technology
  • TRMS measurement
  • Extended supply voltage range
  • 4 ... 20 mA transmitter signal
  • Easy installation

Business data

Order number
AD-SWT 50 SO-TRMS 50 A AC primary current
AD-SWT 100 SO-TRMS 100 A AC primary current
AD-SWT 200 SO-TRMS 200 A AC primary current
Accessory
DIN rail holder 35 mm DIN rail 35mm
Identifiers
Customs tariff number / country of origin 8504 31 29 / Deutschland

Information

Downloads
Data sheet pdf en-swt_trms.pdf (134 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Primary current
Measurement method Inductive
Sample rate 1 kHz (20 measurements / mains period)
Max. measurable harmonic 10 (500 Hz)
Calculation method Root mean square TRMS
Short-term overload (1 s) Twenty times of the nominal value
Permanent overload (24 h) 120 % of the nominal value
Measuring range 0 ... 50/100/200 A AC (50 Hz)
Max. conductor diameter 23 mm
Transmitter output
Output range 4 ... 20 mA
Residual ripple 30 µAss
Transmitter-supply
Voltage range DC 10 ... 30 V DC
Nominal voltage DC 24 V DC
Transmission behaviour
Basic accuracy < 0,5 % (at fundamental 50 Hz)
Temperature influence 100 ppm/K
Response time < 1 s (10...90 %)
Housing
Dimensions (WxHxD) 50x42x82 mm
Type of protection IP 20
Connection method Screw clamp
Terminals, wire cross section 1,5 mm² flex wire / 2,5 mm² one wire
Bolting torque terminals 0,5 Nm
Weight ~ 200 g
Manner of fastening Folding transducer housing
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1 1)
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Safety measurement 61010-2-030
Measurement category CAT III
Galvanic isolation, test voltages
Input / output 4 kV, 50 Hz (1 min.) + insulation of the primary wire
Protection circuits
Output Electrical surge and reverse current protection
1) During checking, slight signal deviations are possible.

Block and wiring diagram

AD-SWT 50 SO-TRMS, AD-SWT 100 SO-TRMS, AD-SWT 200 SO

Dimensions

AD-SWT 50 SO-TRMS, AD-SWT 100 SO-TRMS, AD-SWT 200 SO

CAD / CAE Daten

Under "Generate CAD", select the desired CAD model for this product.
For this purpose, registration with our CAD database "PARTcommunity" is required.
The complete CAD product overview can be found at: adamczewski.partcommunity.com

AD-SWT 50 SO-TRMS

Cookie settings
made with ♡ by andres.media