AD-VarioControl, AD-VarioConnect

Description

The removable control modules AD-VarioControl are used to display measured values of a base device (transmitter, isolation amplifiers ...) with a relevant interface. After plugging in, which is also possible during operation of the base device without restrictions, the basic device is automatically read out and the corresponding measured value is displayed. In addition to the display function, access to the parameters and controller functions of the basic device is also possible. The parameter settings can be loaded into the control panel using the backup function and can be restored on a different base device of the same type.
Establishment of a transmitter is usually necessary only once in the operating period of a device, therefore a display and operating elements are not permanently necessary for each device. By using the AD-VarioControl in connection with compatible basic equipment, operating elements and displays on each individual device can be dispensed with. This way, the installed devices are tamper-proof and more cost-effective.
The AD-VarioConnect has a fieldbus interface with the protocol Modbus-RTU via RS485. All measured values of the basic units are available above this.

AD-VarioControl, AD-VarioConnect

Application

Control device to display and configuration of DIN rail devices with optional fieldbus.

Specific characteristics

  • Removeable (hot-plugged)
  • Store and restore of parameters
  • LCD for display of different operating modes, lit in several colours (R/Y/B)
  • Menu languages switchable to: German, English
  • Simulation modus
  • Fieldbus interface with Modbus RTU (AD-VarioConnect)

Business data

Order number
Control panel AD-VarioControl
Control panel with RS485 AD-VarioConnect
Basic devices
Frequency measuring converter AD-FM 255 GVD
Limit-Switch AD-MK 350 GVD
Temperature Measuring Converter AD-MV 550 GVD
Power measurement transducer AD-LU 320 GVD / AD-LU 325 GVD
Power measurement transducer AD-LU 620 GVF / AD-LU 625 GVF
Isolation amplifier AD-TV 400 GVD
Isolation amplifier AD-TV 420 GVD
AC Isolation Amplifier AD-TV 588 GVD
Multifunction transducer AD-VC 1 GVD
Identifiers
EClass 27210300
Customs tariff number / country of origin 8531 20 40 / Deutschland

Information

Technical specifications

Display
Type LCD graphic
Dimensions (WxH) 18x13 mm
Resolution 42X56 Pixel
Lighting RGB
Operation
Type 3 short-stroke keys
RS485 Bus (Varioconnect)
Protocol Modbus-RTU
Data format (default) 19200, e, 8, 1
Max. bus users 32
Bus termination 120 ohms both sides at the end
Max. length of bus 500 m (no stubs)
Cable Twisted and shielded
Supply
Supply voltage 5 DC
Max. power consumption 0,2 W
Housing
Dimensions (WxHxD) 20x86x14 mm
Dimensions with clamp 20x95x14 mm
Type of protection IP 20
Weight 20 g
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
Electrical safety requirements
Product family standard EN 61010-1
Galvanic isolation, test voltages (VarioConnect)
RS485-bus to basic device 1,5 kV

Block and wiring diagram

AD-VarioControl, AD-VarioConnect

Dimensions

AD-VarioControl, AD-VarioConnect

CAD / CAE Daten

Under "Generate CAD", select the desired CAD model for this product.
For this purpose, registration with our CAD database "PARTcommunity" is required.
The complete CAD product overview can be found at: adamczewski.partcommunity.com

Select CAD model:

Cookie settings
made with ♡ by andres.media