AD-VC 5 GVF

Description

The digital temperature measuring converter of series VarioCheck VC5B are freely programmable digital measuring transducer with two analogue outputs and up to 4 limiting value relays. The input of all characteristics directly on the device, or use the configuration software „AD-Studio“. VarioCheck fulfils all tasks of a universal measuring value recording through integral function modules such as selectable relay functions, simulation modus, free linearizing curves and a wide range of supply voltage.

AD-VC 5 GVF

Specific characteristics

  • Resistance thermometer inputs, types Pt/Ni 100, Pt/Ni 500, Pt/Ni 1000
  • Thermocouples inputs, types J, T, K, E, N, S, R, B, C or inputs a mV/T-characteristic curve. Selectable internal or external reference junction
  • A bipolar mV-Voltage input. Free linearizing curves possible.
  • Current- and voltage input different scaleable and simultaneously useful. Must not conntect the clamps 8 and 9.
  • Galvanic 3-circuit separation of input, output and supply.
  • LCD for display of different operating modes, lit in several colours (R/Y/B).
  • Freely definable scaling of the quantity to be measured through stating range, decimal point position and unit from the list or defined unit.
  • Zoom function, expanded scale, linearizing, inverse modus.
  • Monitoring of the measuring signal with up to 4 freely adjustable limiting values.
  • Monitoring functions such as limiting values, window function or signal trend each with relay.
  • Non-volatile saving of all set parameters.

Business data

Order number
AD-VC 5 GVF-R0 Without relay
AD-VC 5 GVF-R2 Two relays
AD-VC 5 GVF-R4 Four relays
Identifiers
EClass 27210129
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Data sheet pdf en-vc5.pdf (227 kB)
Instruction manual pdf man-vc5-ad-en.pdf (347 kB)
Tender text zip vc5gvf.zip (1 kB)
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Resistance thermometer inputs Pt100, Pt500, Pt1000 to DIN EN 60751
Measuring range -200 ... +850 °C
Connection method 2-, 3- oder 4-wire system
Resolution 16 Bit
Accuracy 0,5 K
Smallest measuring spans 20 K
Max line resistance 1) 10 Ohm/cable
Sensor supply
Pt100 1 mA
Pt500, Pt1000 210 µA
1) With 2-conductor the line resistance comes as an offset into the measurement.
Resistance thermometer inputs Ni100, Ni500, Ni1000 to DIN EN 43760
Measuring range -60 ... +230 °C
Connection method 2-, 3- oder 4-wire system
Resolution 16 Bit
Accuracy 0,5 K
Smallest measuring spans 20 K
Max line resistance 1) 10 Ohm/cable
Sensor supply
Ni100 1 mA
Ni500, Ni1000 210 µA
1) With 2-conductor the line resistance comes as an offset into the measurement.
Thermocouples
Comparative place:
Internal Measurement with LM35 in the device connecting terminals
External Cold junction temperatureselectable by parameters
Resolution 16 Bit
Accuracy 0,2 % of measuring range
Measuring range type J -200 ... +1200 °C
To DIN EN 60584:
Measuring range type T -200 ... +400 °C
Measuring range type K -200 ... +1360 °C
Measuring range type E -200 ... +1000 °C
Measuring range type N -200 ... +1300 °C
Measuring range type S -40 ... +1760 °C
Measuring range type R -40 ... +1760 °C
Measuring range type B +400 ... +1800 °C
After standard ASTM E988:
Measuring range type C 0 ... +2320 °C
Smallest measuring spans 100 K
Voltage inputs
Measuring ranges -18 ... +18 mV
-36 ... +36 mV
-72 ... +72 mV
-144 ... +144 mV
Current output 20 mA
Output range 0 ... 20,4 mA
Resolution 10 Bit
Accuracy 20 µA
Max. burden 500 Ohm
Residual ripple 20 µAss
Voltage output 10 V
Output range 0 ... 10,2 V
Resolution 10 Bit
Accuracy 10 mV
Min. burden 5 kOhm
Residual ripple 10 mVss
Werden Stromausgang und Spannungsausgang gleichzeitig benutzt, dürfen die beiden Kreise nicht verbunden werden.
Relay outputs A..D
Max switching voltage AC 250 V AC
Max switching current AC 2 A AC
Max switching voltage DC 50 V DC
Max switching current DC 2 A DC
Display
Graphic-LCD 42x64 Pixel, background RGB lights
Digital display 4-digit, can be configured
Display function Scaled input signal, input signal, output, limits, scaled dimension as quasi analogue bar, scaling unit
Transmission behaviour
Sampling rate 1 measure/s
Linearity error 0,2 % of full scale
Temperature influence +/-100 ppm/K of full scale
Supply
Supply voltage 50 ... 253 V AC
20 ... 253 V DC
Max power consumption at 24V DC 2,6 W
Max power consumption at 230V AC 5 VA
Housing
Dimension BxHxT 33x110x128 mm
Manner of fastening DIN rail mounting 35mm, EN 50022
Type of protection IP 20
Connection method Detachable terminal clamp, 5 mm grid
Wire cross section Max. 2,5 mm2
Weight Ca. 200 g
Environmental conditions
Permissible ambient temperature -10 ... +60 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard 1) EN 61326-1
Emitted interference EN 55011, CISR11 Cl. B, Gr. 1
1) Während der Störeinwirkung sind geringe Signalabweichungen möglich.
Electrical safety requirements
Product family standard EN 61010-1
Galvanic isolation, test voltages
Input to output 2,5 kV, 1min
Input/output to auxiliary voltages 4 kV, 1min
Outputs together Nogalvanic isolation
Input to the programming interface Nogalvanic isolation

Block and wiring diagram

AD-VC 5 GVF

Dimensions

AD-VC 5 GVF

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com